4 / 20
0006081437_201005
E
N
G
L
I
S
H
TECHNICAL SPECIFICATIONS
TBG 35 PN
THERMAL CAPACITY
MAX
kW
410
MIN
kW
80
OPERATION
Modulating / Progressive two
stage burner
NOx EMISSIONS
mg/kWh
< 80 (Class III according to EN
676)
FAN MOTOR
kW
0,37
r.p.m.
2760
ABSORBED ELECTRICAL POWER*
kW
0,56
IGNITION TRANSFORMER
26 kV - 40 mA - 230/240 V - 50/60
Hz
POWER SUPPLY VOLTAGE
1N ~ 230 V ±10%- 50 Hz
PROTECTION RATING
IP 40
FLAME DETECTOR
IONIZATION PROBE
NOISE**
dBA
76
WEIGHT
kg
40
Natural Gas (G 20)
FLOW RATE
MAX
m³n/h
41,23
MIN
m³n/h
8,05
PRESSURE
MAX
mbar
360
*) Total absorption at start with ignition transformer on.
**) Noise levels measured in the laboratory of the manufacturer with burner running on test boiler, at maximum nominal
thermal output.
STANDARD ACCESSORIES
TBG 35 PN
BURNER COUPLING FLANGE
2
INSULATING GASKET
1
STUD BOLTS
N° 4 M 12
HEXAGONAL NUTS
N° 4 M 12
FLAT WASHERS
N° 4 Ø 12
CONSTRUCTION CHARACTERISTICS
The burner consists of the following parts:
• Air intake with butterfly gate for adjusting the combustion air flow
rate.
• Mounting flange to the sliding generator, to adapt the protuberance
of the head to various types of heating generators.
• Air pressure switch to ensure the presence of combustion air.
• Minimum and maximum air flow adjustment for first and second
stage by means of electric servomotor.
• Gas train complete with security valve and proportional function
-
ing, pneumatic functioning, minimum pressure switch, pressure
regulator and gas filter.
• Flame detection by ionisation electrode.
• Automatic command equipment and burner control according to
European regulation EN298.
• Connection to gas train with fail safe connectors.
• 7 pole plugs for the electricity and thermostat supply of the burner,
4 pole plug for the command of the second stage of functioning
or electric power regulator.
• Suitable for microammeter connection to the ionisation cable.
• Electrical protection rating IP40.