1 / 50
00060812_200712
Legend:
1- Diffuser
2- Deflector disk
3- Nozzle holder
4- Ignition electrodes
5- Nozzle
ELECTRODES/IONISATION PROBE ADJUSTMENT DIAGRAM
After having installed the nozzle, check the correct position of the electrodes and disk according to the following levels. It’s adviseable to
check levels after every intervention on head.
N.B. To prevent damage to the support effect nozzle assembly/disassembly tasks with the aid of a wrench and counter-
wrench.
RECOMMENDED NOZZLES:
DANFOSS S 60° (TBL 45P)
DANFOSS S 45° (TBL 60P)
N.B. The use of an ionisation angle of 45° may significantly improve combustion values with certain applications (e.g. narrow com-
bustion chambers).
Model
A
B
C
D
E
TBL 45P
1 ÷ 2
21
7
5
6,5
TBL 60P
1 ÷ 2
21
7
5
6,5
N°0002935430
REV.: 26/11/07