INSTRUCTIONS LFL 1.... CONTROL BOX
N°
7
451
Rev. 10/1997
Control box for burners of average and high power, with forced draught, intermittent service (*), 1 or 2
stages, or modulating types, with supervision of the air pressure for controlling the air damper.
This control box bears the EC mark, in accordance with the Gas and Electromagnetic Compatibility Directive.
* For reasons of safety, it is necessary to make at least one controlled stop every 24 hours!
As regards the standards
The following LFL1… features exceed the standards, offering a high level of additional safety:
- The flame detector test and false flame test start immediately after the tolerated post-combustion time. If the
valves remain open, or do not close completely after adjustment stops, a lock-out stop is triggered at the end of
the tolerated post-combustion period. The tests will end only at the end of the pre-ventilation time of the next start-
up.
- The validity of working of the flame control circuit is checked each time the burner starts up.
- The fuel valve control contacts are checked for wear during the post-ventilation time.
- A built-in fuse in the appliance protects the control contacts from any overloads that may occur.
As regards the burner control
- The equipment allows operation with or without post-ventilation.
- Controlled activation of the air damper to ensure pre-ventilation with nominal airflows. Positions checked: CLOSED
or MIN (position of ignition flame on start-up); OPEN at the beginning and MIN at the end of the pre-ventilation
time. If the servomotor does not position the air damper at the points described, the burner does not start-up.
- Ionization current minimum value = 6mA
- UV cell current minimum value = 70mA
- Phase and neutral must not be inverted.
Summary of Contents for GI 1000 DSPN-D
Page 23: ...23 ITALIANO SCHEMA DI PRINCIPIO REGOLAZIONE ARIA PER MODELLO GI 1000 DSPN D N 0002933410...
Page 24: ...24 ITALIANO SCHEMA DI PRINCIPIO REGOLAZIONE PILOTA GAS PER MODELLO GI 1000 DSPN D N 0002933930...
Page 50: ...50 ENGLISH BURNER GI 1000 DSPN D AIR FEEDING ADJUSTMENT PRINCIPLA DIAGRAM N 0002933410...
Page 51: ...51 ENGLISH N 0002933930 BURNER GI 1000 DSPN D GAS PILOT ADJUSTMENT PRINCIPLE DIAGRAM...
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......