ENGLISH
14 / 36
0006080872_201711
INTAKE SUPPLY SYSTEM
3
7
10
4
H
6
1
0002900740N3
1 Tank
3
Mesh filter
4 Pump
6
Suction pipe
7
Return pipe
10 Foot valve
H height
Length total metres
m
Øi = 10 mm
Øi = 12 mm
0,5
15
27
1
12
23
1,5
9
19
2
7
15
2,5
4
10
3
-
7
3,5
-
-
H - Height difference between minimum tank level and pump axis.
L - Total length of pipeline, including vertical length. Deduct 0.25 for each
elbow or gate.
CAUTION / WARNING
For any components missing in the pipes, comply with current
regulations.