23 / 47
0006080735_2008/06
N° 0002900860
Rev. 27/07/99
H
= Measurement between minimum oil level and pump axis
L
= Max. legth of suction line, including vertical lifts. For each bend of valve deduct 0,25 m.
Ø i
= Internal diameter of pipe
Quote P = 3,5 m (max)
GRAVITY FEED FROM THE BOTTOM OF OIL TANK
1
Oil tank
6
Suction line
2
Feed line
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
5
Degasifier
SUCTION FEED
1
Oil tank
6
Suction line
3
Filter
7
Return line
4
Burner
10
Foot valve
GRAVITY FEED OVER THE TOP OF OIL TANK
1
Oil tank
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
6
Suction line
10
Foot valve
HYDRAULIC CONNECTIONS
The pipes that connect the tank tothe burner should be in perfect tight condition; we recommend the use of copper or steel pipes
of an adeguate diameter.Fuel gate valves should be fitted at the end of the rigid pipelines.Fit the filter to the suction pipeline
after the gate valve. Connect the flexible fitting to this, which in turn should be connected to the suction of the burner pump.
Connect the flexible fitting to the return pipe after the gate valve, and then connect it ot the pump return. Filter, flexible pipes
and relative connecion nipples are standard burner accessories. The pump is provided with special connection points for the
insertion of control instruments (manometer and vacuumeter).To ensure reliable and silent operating conditions, the vacuum
in suction should not exceed 35 cm Hg equal to 0,46 bar.Maximun suction and return pressure 1,5 bar.
N.B. For any missing devices in the
pipping, conform to existing regulations.
H
Total meters
meters
Ø i. 10 mm.
1
30
2
35
3
40
4
45
H
Total meters
meters
Ø i. 10 mm.
1
30
2
35
3
40
4
45
H Total meters
meters
Ø i. 10 mm. Ø i. 12 mm.
0,5
26
54
1
24
47
1,5
18
38
2
14
30
2,5
10
23
3
6
15
3,5
-
7
Summary of Contents for BTL 3