AIR SHUTTER CONTROL SERVOMOTOR
1 Wiring diagram
2 Screw adjustment
3 Second stage air regulation cam (precalibration at 30°)
4 First stage air regulation cam (precalibration at 20°)
5 Second stage valve control CAM (must be set between the 1st
stage and 2nd stage cam)
6 Electrical connections
7 Reference index
To modify the adjustment of the cams operate the respective screws.
The pointer on the red ring indicates the rotation angle set for each
cam on the respective reference scale.
18 / 28
0006160466_202205
ENGLISH
Summary of Contents for BTL 10P
Page 2: ......
Page 29: ...SCHEMI ELETTRICI 27 28 0006160466_202205 ITALIANO ...
Page 57: ...WIRING DIAGRAMS 27 28 0006160466_202205 ENGLISH ...
Page 59: ......