TECHNICAL SPECIFICATIONS
MODEL
BTL 4P
BTL 6P
BTL 10P
Minimum flow rate
Kg/h
2.2
2.7
5.1
Maximum flow rate
Kg/h
4.7
6.3
10
Minimum thermal power
kW
26
31.9
60.2
Maximum thermal power
kW
56.1
74.3
118
³) emissions
mg/kWh
Class 2
Class 2
Class 2
Viscosity
1,5° E - 20° C - 5,5 cst/
20° C
1,5° E - 20° C - 5,5 cst/
20° C
1,5° E - 20° C - 5,5 cst/
20° C
Operation
Two-stage
Two-stage
Two-stage
50hz transformer
40 mA - 2x7,5kV
40 mA - 2x7,5kV
40 mA - 2x10kV
60hz transformer
40 mA - 2x7,5kV
40 mA - 2x7,5kV
40 mA - 2x10kV
50hz fan motor
kW
0.1
0,1,
0.1
50hz fan motor rpm
2750
2750
2750
60hz fan motor
kW
0.1
0.1
0.1
60hz fan motor rpm
3300
3300
3300
50Hz three-phase electrical data
0.18
0.18
0.18
60Hz three-phase electrical data
0.18
0.18
0.18
50Hz single-phase electrical data
1N - 230V - 1,46A -
0,336kW
1N - 230V - 1,46A -
0,336kW
1N - 230V - 1,46A -
0,336kW
60Hz single-phase electrical data
1N - 230V - 1,46A -
0,336kW
1N - 230V - 1,46A -
0,336kW
1N - 230V - 1,46A -
0,336kW
Protection rating
IP40
IP40
IP40
Control box
LMO 24
LMO 24
LMO 24
Flame detection
Photoresistor
Photoresistor
Photoresistor
Air flow rate regulation
Air servomotor
Air servomotor
Air servomotor
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
64.2
64.5
65.1
Weight with packaging
kg
12
12
12
Weight without packaging
kg
11
11
11
Lower calorific power:
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
TYPE OF NOZZLE OR EQUIVALENT
BTL 4P - 6P - 10P
DANFOSS B 60° DELAVAN W 60°
³) DIESEL EMISSIONS
Classes defined according to EN 267 standards.
Class
NOx emissions in mg/kWh diesel fuel
CO emissions in mg/kWh diesel fuel
1
≤ 250
≤ 110
2
≤ 185
≤ 110
3
≤ 120
≤ 60
6 / 28