TECHNICAL SPECIFICATIONS
MODEL
BTG 3,6
BTG 6
BTG 11
Maximum natural gas heat power
kW
41.9
56.3
99
Minimum natural gas heat power
kW
16.3
30.6
48.8
¹) natural gas emissions
mg/kWh
Class 2
Class 2
Class 2
Operation
single-stage
single-stage
single-stage
50 Hz natural gas transformer
15kV - 25mA
15kV - 25mA
15kV - 25mA
Methane maximum flow rate
Stm³/h
4.4
6
10.5
Methane minimum flow rate
Stm³/h
1.7
3.2
5.2
Maximum natural gas pressure
hPa (mbar)
65
65
65
Minimum natural gas pressure
hPa (mbar)
9
7
15
Maximum propane thermal power
kW
41.9
56.3
99
Minimum propane thermal power
kW
16.3
30.6
48.8
Propane maximum flow rate
Stm³/h
1.7
2.3
4.1
Propane minimum flow rate
Stm³/h
0.7
1.3
2
Maximum propane pressure
hPa (mbar)
65
65
65
Minimum propane pressure
hPa (mbar)
5
7
17
²)propane emissions
mg/kWh
Class 2
Class 2
Class 2
50hz fan motor
kW
0.1
0.1
0.1
50hz fan motor rpm
r.p.m.
2800
2800
2800
50Hz single-phase electrical data
1N - 230V - 1,640A -
0,377kW
1N - 230V - 1,64A -
0,377kW
1N - 230V - 1,64A -
0,377kW
Protection rating
IP40
IP40
IP40
Flame detection
IONISATION PROBE
IONISATION PROBE
IONISATION PROBE
Control box
LME 11...
LME11..
LME11..
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
64
64
64
Weight with packaging
kg
12
12
12
Weight without packaging
kg
10.75
10.75
10.75
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
Classes defined according to EN 676 standards.
Propane / natural gas CO emissions ≤ 100 mg/kWh
¹) NATURAL GAS EMISSIONS
Class
NOx emissions in mg/kWh natural gas
1
≤ 170
2
≤ 120
3
≤ 80
4
≤ 60
²) PROPANE GAS EMISSIONS
Class
NOx emissions in mg/kWh propane gas
1
≤ 230
2
≤ 180
3
≤ 140
4
≤ 110
6 / 30
0006080749_202206