![background image](http://html1.mh-extra.com/html/baltur/btg-15/btg-15_instruction-manual-for-installation-use-and-maintenance_4019950058.webp)
MAINTENANCE
Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
•
Check that the fuel filter is clean. Replace it, if necessary.
• Check the electrode condition. Replace them, if necessary.
•
Having completed the maintenance work, replace the combustion
head, following in reverse order the operations described above,
after having checked the correct position of ignition and ionisation
electrodes.
Most components can be inspected by removing the hood. To inspect
the head you must disassemble the component-carrying plate which
can be hung on hung on the burner body in two different positions to
make work as practical as possible.
M
anut
enzione_1
Undo the lid screw to gain access to the interior of the burner.
FAN ASSEMBLY DIAGRAM
During fan assembly, check that the dimension indicated is respected.
Manutenzione_2
After disconnecting the gas train, unscrew the three screws (B) that
fasten the flange of the gas delivery fitting to the burner plate.
Manutenzione_3
Remove the mixing unit.
ENGLISH
24 / 32
0006080876_201912
Summary of Contents for BTG 15
Page 2: ......
Page 33: ...SCHEMI ELETTRICI ITALIANO 31 32 0006080876_201912...
Page 65: ...WIRING DIAGRAMS ENGLISH 31 32 0006080876_201912...