OPERATING ANOMALY
TYPE OF IRREGULARITY
SOLUTION
BPM 90 / 140 / 250 / 300 / 350 EVO
The burner does not start
- Check the supply voltage;
- Check the regulation thermostat (TC);
- Check that the connectors are properly inserted.
- Check that the network fuse is intact.
- Check the gas inlet pressure (2):
- Press the reset key.
- Check the gas valve opening; if the valve does not open a pressure drop
will occur in point (2).
- Check the ignition electrode (see electrodes position chapter)
- Check the ionisation current if there is not any.
The burner ignites, the ionisation current is present but after the safety
time the burner turns off.
- Check that the phase and neutral positions have been respected.