OPERATING ANOMALY
TYPE OF IRREGULARITY
Burner doesn't start
RIMEDY
- Verify voltage supply
- Verify regulation thermostat (TC)
- Verify proper plugs' insertion
- Verify fuse integrity
- Verify inlet gas pressure (2)
- Pushing reset button (1)
- Verify valve's opening; ; if the safety valve opens there will be a
fall in pressure at point (2);
- Verify ignition electrodes;
- Verify the ionisation's current is null.
TYPE OF IRREGULARITY
Burner ignite, ionisation's current is present but, after safety time,
burner stops.
RIMEDY
- Verify proper electrical connection, phase and
neutral.
2
1
3,5-4,5 mm.
3