23
Mod. MVDLE....
Mod. MVD....
8875.tif
H
= Identification plate
I
= Flow direction indicator
D
= Identification plate
E
= Flow direction
indicator
N° 8875-GB
Rev. 06/11/90
The MVD gas valves open and close rapidly.
To regulate the gas flow, unscrew and remove cap
“A” and loosen nut “B”.
Then, using a screwdriver turn screw “C”.
Unscrewing it increases the gas flow, tightening it
decreases the flow.
After regulating, lock nut “B” in place and reposition
cap “A”.
HOW THE VALVE FUNCTIONS mod. MVDLE
The gas valve has a rapid initial trip (opening can
be adjusted from 0 to 40% using pin “G”). Full
opening from that point on takes place slowly over
approximately 10 seconds.
N.B.
There will not be sufficient supply for ignition if
the flow feed device “E” is set at its minimum
position. Therefore, it is essential to open the
maximum flow rate control device “E” sufficiently
to ensure ignition.
Setting the initial rapid release trip
To set the initial rapid release, unscrew the protection
cap “F” and use the back of this cap as a tool to turn
pin “G”.
Turning clockwise decreases the gas flow, turning
counter-clockwise increases it.
This done, return cap “F” to its original position.
Setting maximum gas flow
To adjust the gas flow rate, loosen screw “D” and
turn knob “E”. Turning clockwise decreases the gas
flow, turning counter-clockwise increases it.
This done, tighten screw “D”.
INSTRUCTIONS FOR SETTING DUNGS GAS
VALVES mod. MVD ... and MVDLE ...
Summary of Contents for BGN 100 DSPGN
Page 6: ...6 BGN 40 DSPGN 100 DSPGN N 7604 2 Rev 02 02 96 BGN 120 DSPGN 350 DSPGN N 7605 5 Rev 17 11 97...
Page 19: ...19 AIR REGULATION PRINCIPLE DIAGRAM FOR GAS BURNERS BT 8769 1...
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......