ENGLISH
6 / 34
0006081532_201711
TECHNICAL SPECIFICATIONS
MODEL
TBG 45 ME
TBG 60 ME
MAXIMUM NATURAL GAS HEAT POWER
kW
485
682
MINIMUM NATURAL GAS HEAT POWER
kW
89
103
¹) NATURAL GAS EMISSIONS
mg/kWh
<80 (Class 3 according to EN
676)
<80 (Class 3 according to EN
676)
OPERATION
Two-stage progressive /
modulating
Two-stage progressive /
modulating
NATURAL GAS TRANSFORMER 50 Hz
26 kV - 40 mA - 230/240 V
26 kV - 40 mA - 230/240 V
NATURAL GAS TRANSFORMER 60 Hz
26 kV - 40 mA - 230/240 V
26 kV - 40 mA - 230/240 V
MAXIMUM NATURAL GAS HEAT RATE
Stm³/h
45.3
60.3
MINIMUM NATURAL GAS HEAT RATE
Stm³/h
10.1
12.1
MAXIMUM NATURAL GAS PRESSURE
hPa (mbar)
360
360
NATURAL GAS MINIMUM PRESSURE
hPa (mbar)
18.5
20
PROPANE GAS MAXIMUM THERMAL POWER
kW
555
676
PROPANE GAS MINIMUM THERMAL POWER
kW
92
85
PROPANE GAS MAXIMUM PRESSURE
hPa (mbar)
360
360
PROPANE GAS MINIMUM PRESSURE
hPa (mbar)
22.5
29
50 Hz FAN MOTOR
kW
0.5
0.75
50Hz FAN MOTOR RPM
r.p.m.
2730
2800
ABSORBED ELECTRICAL POWER* 50Hz
kW
0.7
0.97
50 Hz POWER SUPPLY VOLTAGE
1N~ 230V ± 10%
3N~ 400V ± 10%
DEGREE OF PROTECTION
IP 40
IP 40
FLAME DETECTOR
IONISATION PROBE
IONISATION PROBE
AIRFLOW REGULATION
ELECTRONIC CAM
ELECTRONIC CAM
SOUND PRESSURE**
dBA
73
78.8
SOUND POWER***
dBA
-
87.5
CO emissions, natural gas/propane ≤ 100 mg/kWh
Calorific power lower than reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9.45 kWh/Stm³ = 34.02 MJ/Stm³
Propane gas: Hi = 24.44 kWh/Stm³ = 88.00 MJ/Stm³
For different types of gas and pressure values, please contact our sales department.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
* Total absorption at start with ignition transformer on.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory
environment conditions and cannot be compared to measurements carried out in different locations.
*** Acoustic power was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2
accuracy (engineering class) with a standard deviation of 1.5 dB(A).
¹) NATURAL GAS EMISSIONS
Classes defined according to Standard EN 676.
Class
NOx emissions in mg/kWh - natural gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE EMISSIONS
Classes defined according to Standard EN 676.
Class
NOx emissions in mg/kWh - propane gas
1
≤ 230
2
≤ 180
3
≤ 140
Summary of Contents for 17230020
Page 2: ......
Page 32: ...ITALIANO 30 34 0006081532_201711 SCHEMI ELETTRICI ...
Page 33: ...ITALIANO 31 34 0006081532_201711 ...
Page 34: ...ITALIANO 32 34 0006081532_201711 ...
Page 36: ......
Page 66: ...ENGLISH 30 34 0006081532_201711 WIRING DIAGRAMS ...
Page 67: ...ENGLISH 31 34 0006081532_201711 ...
Page 68: ...ENGLISH 32 34 0006081532_201711 ...
Page 70: ......
Page 71: ......