  •  1-800-543-8390

  

To enter the 

Programming Mode

, press the 

<PGM + UP

> keys simultaneously for at least 3 seconds.  

Programming Mode allows the user to adjust the following parameters: 

 

 

Set Units -

 The display shows the position value in either Millimeters or Inches.  

For Millimeters press the 

<UP>

 key, for Inches, press the 

<DOWN>

 key.  The 

default value is Inches.  Press 

<PGM> 

to continue to the next parameter. 

 

 

 

Adjust Update rate -

 This menu allows the update rate to be set (Sampling 

Rate) to either 1mSec or 2mSec.  For a 1mSec update rate, press the 

<DOWN>

 

key.  For a 2mSec update rate, press the 

<UP>

 key.  The default value is 

1mSecs.  Press 

<PGM> 

to continue to the next parameter.  

 

 

 

 

Adjust Gradient -

 Enter the gradient of the transducer.  The gradient value is 

found on the Balluff transducer label in “µs/in” (e.g. grad=8.8843µs/in).  Initially 
the gradient value is set to 9.0000 µs/in with the last digit blinking.  Press the 

<UP>

 key to increment this value to the desired setting.   Press 

<SEL>

 to move 

the cursor to the next digit.  Press the 

<UP>

 and 

<DOWN>

 keys to adjust each 

digit.  Continue this process until all of the digits are set according to the gradient 
value marked on the label.  Press 

<PGM>

 to continue to the next parameter.

 

 

 

 

 

 

 

1. 

2. 

3. 

4. 

Adjust Nominal Stroke -

 This menu allows the operator to enter the Nominal 

Stoke length of the transducer.  This will also adjust the NULL and GAIN values 
to approximate settings.  Exact setting of the NULL and GAIN values will be set 
during the 

Online Adjust

 

Mode 

programming.   Initially the value is set to 060.0

 

in, with the cursor blinking in the least significant number.  Adjust this value ac-
cordingly, using the 

<UP>

 and 

<DOWN>

 keys.  Press the

 <SEL> 

key to ad-

vance to the next significant number.  Follow this process until the value is cor-
rectly entered.  Press 

<PGM>

 to continue to the next parameter.  

Note - When 

replacing an existing position transducer, set the nominal stroke to the same 
value as that of the transducer being replaced.

 

 

 

5. 

Set PWM State -

 This will allow the Pulse Width Modulated output signal to be 

either Active high or Active low.  For Active high, press the 

<UP> 

key.  For Ac-

tive low, press the 

<DOWN>

 key.  The default state is Active low

.

  Press 

<PGM>

 

to continue to the next parameter.  

Note -

 

This step is not needed if only the 

analog output is being used

.

 

 

 

6. 

Adjust Number of Recirculations - 

The number of recirculations of the PWM 

output signal can be set between 1 and 16, default is 01.  Use the 

<UP>

 or 

<DOWN>

 key to adjust the number to the desired value.  Press 

<PGM>

 to con-

tinue to the next parameter.  

Note -

 

This step is not needed if only the analog 

output is being used.

 

 

 

 

7. 

Set Analog State -

 This allows the user to program the slope of the analog out-

put voltage.  Press the 

<UP>

 key for Output Rising (-10 to +10Vdc) or press the 

<DOWN>

 key for Output Falling (+10 to -10 Vdc).  Rising and falling values are 

based on the magnet reading starting at the Null position closest to the electron-
ics.  The default setting is Output Rising. Press the 

<PGM>

 key to exit Program-

ming Mode and return to Run Mode. 

 

 

 

 

Programming Mode 

Summary of Contents for MICROPULSE BTM-AR2-001

Page 1: ...BTM AR2 001 Transducer Interface Module...

Page 2: ...d PWM position output signals The BTM AR2 001 module is user programmable to meet a wide variety of application requirements The BTM AR2 001 interface module and Micropulse linear position transducers...

Page 3: ...acement transducer w Start Stop interface Output Signals Analog Voltage 10Vdc to 10 Vdc Adjustable PWM Operating Voltage and 15 Vdc 2 Transducer Supply Voltage 24 Vdc supplied by interface module Oper...

Page 4: ...er can be used to adapt the BTM AR2 001 Interface Module to non standard mounting surfaces If the mounting plate adapter is not required it may be discarded Mechanical Dimensions and Installation Inst...

Page 5: ...luff com 1 800 543 8390 5 Up Button Down Button SEL Button PGM Button Green Program LED Red Error LED Information Card J1 Power Output Con nector Balluff Transducer LCD Display Internal Layout User Co...

Page 6: ...e and transducer are working properly both the green program LED and the red error LED will be off Setup Instructions Factory Default Settings To enter the Configure Mode press the PGM DOWN keys simul...

Page 7: ...the NULL and GAIN values will be set during the Online Adjust Mode programming Initially the value is set to 060 0 in with the cursor blinking in the least significant number Adjust this value ac cor...

Page 8: ...magnet to the Gain position towards the end of the trans ducer rod side that is away from the transducer housing The Gain value may be adjusted anywhere between 10 Vdc 10 Vdc Press the UP key to incr...

Page 9: ...ff canada balluff ca Mexico Balluff de Mexico S A de C V Prol Av Luis M Vega 109 Col Ampliaci n Cimatario Queretaro QRO 76030 Phone 52 442 212 4882 224 3583 224 3171 Fax 52 442 214 0536 E mail balluff...

Reviews: