BNI LH1-303-S11-K091 / BNI LH1-313-S11-K091

Network interface – Digital hub

1.1.2  IO-Link interface (XF1/ )

Fig. 5-1: 

4

3

1

2

Top view of M12 plug, A-coded

Pin

Signal

Supply voltage for the module and connected 

sensors (U

S

)

2

Supply voltage for actuators (U

A

)

3

GND, reference potential

4

C/Q, IO-Link data transmission channel

Tab. 5-1:  Pin assignment of IO-Link interface

1.1.3  I/O-Port (X01…X08)

Fig. 5-2: 

3

5

4

2

1

Top view of M12 socket, A-coded

Pin

Signal

+24 V, sensor supply

2

Digital input/output

3

GND, sensor supply, inputs, outputs

4

Digital input/output

5

Functional earth

Tab. 5-2:  Pin assignment of standard I/O port (X01…X08)

For the digital sensor inputs, see guideline

via inputs EN 61131-2, type 1 and type 3.

1.1.4  Grounding

To counteract EMC interference, the functional earth 

connection must be used.

 

Connect the earth terminal to the functional earth (FE) 

of the machine.

The FE connection between the housing and 

the machine must have a low impedance and 

be as short as possible.

 

Use the grounding strap included in the 

scope of delivery.

Fig. 5-3:  Ground connection

5.3 

Shielding and cable routing

Shielding

The connection to the higher-level IO-Link master and the 

connection to the extension device is made with a 

standard sensor cable.

Since the housings are made of non-conductive 

material, interfering signals cannot flow through 

the shielding to the FE. The shielding of the cable 

should be connected to the FE (functional earth) 

either on the sensor or module side. If connection 

is not possible on the sensor side, the adapter 

cable available from Balluff as an optional 

accessory can be used. The adapter cable routes 

the shielding of the cable to Pin 5 of the port and 

thus to FE.

Digital sensors and actuators are connected to the 

described hubs using standardized, unshielded sensor 
cables.

Cable length

The IO-Link connection cable and the cable for connection 

to the extension device may be max. 20 meters. The 

connection cables between digital sensors and actuators 

and hub may be max. 30 meters.

5

 

Installation and connection (continued)

Summary of Contents for IO-Link BNI LH1-303-S11-K091

Page 1: ...deutsch Betriebsanleitung english User s Guide BNI LH1 303 S11 K091 BNI LH1 313 S11 K091...

Page 2: ...www balluff com...

Page 3: ...BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 Betriebsanleitung deutsch...

Page 4: ...www balluff com...

Page 5: ...eise 6 3 Lieferumfang Transport und Lagerung 7 3 1 Lieferumfang 7 3 2 Transport 7 3 3 Lagerbedingungen 7 4 Produktbeschreibung 8 4 1 Aufbau 8 4 2 Funktion 9 4 3 Anzeigeelemente 10 4 4 Bedruckung 10 5...

Page 6: ...ittstelle digitaler Hub 10 Technische Daten 17 10 1 Umgebungsbedingungen 17 10 2 Elektrische Merkmale 17 10 3 Elektrischer Anschluss 17 10 4 Schnittstelle 17 10 5 Material 17 10 6 Mechanische Merkmale...

Page 7: ...e Kennzeichnung sind Dezimalzahlen z B 23 Hexadezimale Zahlen werden mit vorangestell tem 0x dargestellt z B 0x12AB Hinweis Tipp Dieses Symbol kennzeichnet allgemeine Hinweise 1 4 Bedeutung der Warnhi...

Page 8: ...u Anschluss und Inbetriebnahme d rfen nur durch geschulte Fachkr fte erfolgen Eine geschulte Fachkraft ist wer aufgrund seiner fachli chen Ausbildung seiner Kenntnisse und Erfahrungen sowie seiner Ken...

Page 9: ...m Lieferumfang enthalten und deshalb getrennt zu bestellen Empfohlenes Zubeh r finden Sie unter www balluff com auf der Produktseite 3 2 Transport Produkt in Originalverpackung bis zum Verwendungs ort...

Page 10: ...Netzwerkschnittstelle digitaler Hub 4 1 Aufbau IO Link Port Port 2 Datamatrix Code Port 1 Port 4 Port 3 Port 6 Port 5 Port 8 Port 7 Befestigungsloch mit FE Anschluss Befestigungsloch Bild 4 2 Ger te...

Page 11: ...n dardausg ngen mit einer Leistung von jeweils bis zu 200 mA Leistungs bersicht bei maximaler Belastung Ausgangs strom Sensor versor gung US Aktorversorgung UA Maximal pro Modul 2 A 2 A Ports Maximale...

Page 12: ...Gr n wech selnd mit LED aus im Verh ltnis 10 1 1 s Periode IO Link Kommunikation ist aktiv Das Ger t ist bereit Gr n statisch Keine Kommunikation Tab 4 1 Status LEDs Port Pin Status LEDs Standard Port...

Page 13: ...ungs konzept entsprechend auszulegen ACHTUNG berstrom Defekte oder fehlende Sicherungen in der Spannungsver sorgung f r Sensor und Aktor f hrt zu deren Besch di gung Eine Sicherung oder ein intelligen...

Page 14: ...use und Maschine muss eine niedrige Impedanz aufwei sen und so kurz wie m glich sein Erdungsband aus dem Lieferumfang ver wenden Bild 5 3 Anschluss Erdung 5 3 Schirmung und Kabelverlegung Schirmung D...

Page 15: ...gen Direkten Hautkontakt mit der Oberfl che vermeiden Hinweise zum Betrieb Funktion des BNI und aller damit verbundenen Kompo nenten regelm ig pr fen Zur Erhaltung der Schutzarten kann es je nach Betr...

Page 16: ...igurations Manual Das Modul muss in die Steuerung eingebunden werden Dazu dient die entsprechende IODD Datei Die IODD kann kostenlos unter www balluff com heruntergeladen werden F r eine detaillierte...

Page 17: ...ler I O Hub Digital I O Hub Sekund re Funktionen Spannungs und Strom berwachung Voltage and Current Monitoring Systemfunktionen Ger testatus und detailierter Ger testatus Device Status and detailed De...

Page 18: ...durchge f hrt werden Sollte das Produkt defekt sein nehmen Sie Kontakt mit unserem Service Center auf 9 2 Demontage Ger t nur in spannungsfreiem Zustand demontieren 9 3 Entsorgung Befolgen Sie die nat...

Page 19: ...usgangsstrom 2 A Ausgangsstrom Sensorversorgung Pin 1 500 mA 10 3 Elektrischer Anschluss IO Link Schnittstelle Port M12 A codiert 4 polig Stecker Eingang Ausgangs Ports 8 M12 A codiert 5 polig Buchse...

Page 20: ...NI LH1 313 S11 K091 Netzwerkschnittstelle digitaler Hub 11 Typenschl ssel BNI LH1 303 S11 K091 Funktion 303 16 PNP Eing nge und 8 PNP Ausg nge 313 16 NPN Eing nge und 8 NPN Ausg nge 956425_AB DE D23 n...

Page 21: ...BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 User s guide english...

Page 22: ...www balluff com...

Page 23: ...and storage 7 3 1 Scope of delivery 7 3 2 Transport 7 3 3 Storage conditions 7 4 Product description 8 4 1 Construction 8 4 2 Function 9 4 3 Display elements 10 4 4 Labeling 10 5 Installation and con...

Page 24: ...K091 Network interface Digital hub 10 Technical data 17 10 1 Ambient conditions 17 10 2 Electrical data 17 10 3 Electrical connection 17 10 4 Interface 17 10 5 Materials 17 10 6 Mechanical features 17...

Page 25: ...bers unless otherwise indicated are decimals e g 23 Hexadecimal numbers are represented with a preceding 0x e g 0x12AB Note tip This symbol indicates general notes 1 4 Explanation of the warnings Alwa...

Page 26: ...s such as installation connection and startup may only be carried out by qualified personnel Qualified personnel are persons whose technical training knowledge and experience as well as knowledge of t...

Page 27: ...re not included in the scope of delivery and must be ordered separately Recommended accessories can be found at www balluff com on the product page 3 2 Transport Transport product to location of use i...

Page 28: ...1 Network interface Digital hub 4 1 Construction IO Link Port Port 2 Datamatrix Code Port 1 Port 4 Port 3 Port 6 Port 5 Port 8 Port 7 Befestigungsloch mit FE Anschluss Befestigungsloch Fig 4 2 Device...

Page 29: ...outputs each with a power rating of up to 200 mA Overview of power with maximum load Output current Sensor supply US Actuator supply UA Maximum per module 2 A 2 A Ports Maximum output current per pin...

Page 30: ...in the nominal range IOL Green alternating with LED off in a ratio of 10 1 1 s period IO Link communication is active The device is ready Green static No communication Tab 4 1 Status LEDs Port pin sta...

Page 31: ...design the fuse protection concept accordingly NOTICE Overcurrent Defective or missing fuses in the power supply for sensor and actuator will damage them Use a fuse or an intelligent power supply cur...

Page 32: ...achine must have a low impedance and be as short as possible Use the grounding strap included in the scope of delivery Fig 5 3 Ground connection 5 3 Shielding and cable routing Shielding The connectio...

Page 33: ...d direct skin contact with the surface Operating notes Regularly check function of the BNI and all associated components Depending on the operating conditions it may be necessary to regularly check an...

Page 34: ...the configuration manual The module must be integrated into the control system The corresponding IODD file is used for this The IODD can be downloaded free of charge from www balluff com For a detaile...

Page 35: ...see the configuration guide at www balluff com on the product page Primary functions Identification Digital I O hub Secondary functions Voltage and current monitoring System functions Device status a...

Page 36: ...only be performed by Balluff If the product is defective contact our Service Center 9 2 Disassembly Only disassemble the device when it is de energized 9 3 Disposal Observe the national regulations f...

Page 37: ...Total output current 2 A Sensor supply output current Pin 1 500 mA 10 3 Electrical connection IO Link interface port M12 A coded 4 pin plug Input output ports 8 M12 A coded 5 pin socket 1 As per IEC 6...

Page 38: ...K091 BNI LH1 313 S11 K091 Network interface Digital hub 11 Type code BNI LH1 303 S11 K091 Function 303 16 PNP inputs and 8 PNP outputs 313 16 NPN inputs and 8 NPN outputs 956425_AB EN D23 Subject to...

Page 39: ...BNI LH1 303 S11 K091 BNI LH1 313 S11 K091...

Page 40: ...www balluff com...

Page 41: ...5 1 2 5 1 3 5 1 4 5 1 5 5 1 6 5 2 6 2 1 6 2 2 6 2 3 6 3 7 3 1 7 3 2 7 3 3 7 4 8 4 1 8 4 2 9 4 3 10 4 4 10 5 11 5 1 11 5 2 11 5 2 1 11 5 2 2 IO Link XF1 12 5 2 3 I O X01 X08 12 5 2 4 12 5 3 12 6 13 6 1...

Page 42: ...4 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 10 17 10 1 17 10 2 17 10 3 17 10 4 17 10 5 17 10 6 17 10 7 17 11 18...

Page 43: ...1 1 1 BNI LH1 3_3 S11 K091 18 BNI LH1 303 S11 K091 BNI00J8 BNI LH1 313 S11 K091 BNI00J9 2023 Balluff GmbH 1 2 www balluff com 1 3 1 1 1 2 2 23 0x 0x12AB 1 4 1 5 EMC FE GND Ground I O Port Input Output...

Page 44: ...6 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 2 1 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 2 2 2 3 BNI BNI 2...

Page 45: ...www balluff com 7 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 3 1 IO Link www balluff com 3 2 3 3 17 3...

Page 46: ...8 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 4 1 IO Link 2 1 4 3 6 5 8 7 FE 4 2 4 4 1...

Page 47: ...PNP BNI LH1 313 S11 K091 NPN IO Link 200 mA US UA 2 A 2 A 1 2 01 4 00 1 X01 500 mA 2 X02 500 mA 3 X03 500 mA 4 X04 500 mA 5 X05 500 mA 200 mA 200 mA 6 X06 500 mA 200 mA 200 mA 7 X07 500 mA 200 mA 200...

Page 48: ...10 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 4 4 3 4 3 LED LED 00 4 01 2 LED LED US 1 Hz UA UA 1 Hz IOL LED 10 1 1 IO Link 4 1 LED LED LED 1 Hz 1 3 2 4 3 2 4 1 0 4 2 LED 4 4 4 4 1 2 3 1 2 3 4 5...

Page 49: ...www balluff com 11 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 5 1 4 1 8 www balluff com 2 M4 3 Nm 4 1 8 IP67 0 6 Nm 5 2 5 2 1 US 2 A UA 2 A FE IO Link 5 36 V IO Link IO Link US UA US UA...

Page 50: ...S11 K091 5 2 2 IO Link XF1 5 1 4 3 1 2 M12 A 1 US 2 UA 3 GND 4 C Q IO Link 5 1 IO Link 5 2 3 I O X01 X08 5 2 3 5 4 2 1 M12 A 1 24 V 2 3 GND 4 5 5 2 I O X01 X08 EN 61131 2 1 3 5 2 4 EMC FE FE 5 3 5 3...

Page 51: ...www balluff com 13 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 6 1 BNI 1 2 3 BNI BNI 6 2 BNI 5 1 11 6 3 6 4 5 1 11 6...

Page 52: ...14 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 IODD IODD www balluff com www balluff com 7...

Page 53: ...alluff com Identification I O Digital I O Hub Voltage and Current Monitoring Device Status and detailed Device Status Reset Commands LED LED meaning and configuration Process Data Info and Configurati...

Page 54: ...16 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 9 1 9 2 9 3 www balluff com 9...

Page 55: ...m 10 1 20 60 C 25 70 C IP67 10 2 US 18 30 2 V DC UA 12 30 2 V DC 1 US 24 V 40 mA 31 2 200 mA 2 A 1 500 mA 10 3 IO Link M12 A 4 8 M12 A 5 1 IEC 61131 2 2 10 4 IO Link 1 1 3 COM3 230 4 kBit s 2 ms 6 2 1...

Page 56: ...18 BNI LH1 303 S11 K091 BNI LH1 313 S11 K091 11 BNI LH1 303 S11 K091 303 16 PNP 8 PNP 313 16 NPN 8 NPN 956425_AB ZH D23 C23...

Page 57: ......

Page 58: ...uidling A Yunding International Commercial Plaza 200125 Pudong Shanghai China Headquarters und Technical Service Hub Region EMEA Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Technical...

Reviews: