BTL5-A/C/E/G1_-M/U_ _ _ _-T-_S 32
Micropulse Linear Transducer - Rod Style
10
english
9
Resetting all values (Reset)
If an existing configuration needs to
be deleted, all values can be re-
stored to the original factory set-
tings (Reset).
Note:
The Reset procedure must be
performed individually for each
measuring unit.
Activate buttons:
1. Press one of the buttons for at
least 3 s. Release button.
2. Within 1 s hold down buttons 1+2
simultaneously for at least 3 s. Now
the Error value remains stored as
the output signal.
If an error occurs or there is an
interruption while activating a
button, please wait for an addi-
tional 12 s before starting over.
Perform reset:
3. Hold down both buttons for at least
6 s. The Null value is displayed, and
the reset has taken place.
4. Release buttons. The current posi-
tion value is displayed and the but-
tons are again deactivated.
The transducer is ready for new
calibration.
10.50
V
V
V
0.00
8.43
5.39
5.39
V
V
V
>6 s
3.60
m
A
m
A
15.67
10.80
10.80
m
A
m
A
m
A
m
A
4.00
1
/ 2
1
+ 2
1
+ 2
10.50
3.60
>3 s
<1 s
>3 s
Displayed values (example)
at 0...10 V
at 4...20 mA
Code =
Error value
Code =
Error value
Current
position value
Current
position value
Code =
Null value
Current
position value
(factory set-
ting)
Enable buttons
Reset