Balluff / IO-Link BNI IOL-800-000-Z03x
www.balluff.com
16
5
Technical Data
5.1
Dimensions
BNI IOL-800-000-Z036
BNI IOL-800-000-Z037
5.2
Mechanical data
Housing Material
Polycarbonate transparent - die-cast zinc housing
IO-Link-Port
M12, A-coded, male
Enclosure rating
BNI IOL-800-000-Z036
IP65 (only when plugged-in)
BNI IOL-800-000-Z037
IP30 (only when plugged-in)
Weight
BNI IOL-800-000-Z036 ca. 320 g
BNI IOL-800-000-Z037 ca. 390 g
Dimensions
(L × W × H, excluding connector)
BNI IOL-800-000-Z036: 117 × 60 × 60 mm
BNI IOL-800-000-Z037: 138,5 × 60 × 60 mm
5.3
Electrical data
Operating voltage
18 ... 30,2 V DC, per EN 61131-2
Ripple
<
1 %
Current draw all segments off
≤
30 mA @24V
Current draw all segments white,
buzzer on
BNI IOL-800-000-Z036: ≤ 100 mA @24V
BNI IOL-800-000-Z037: ≤ 110 mA @24V
Volume of the buzzer module
100dB at 1m distance
Tone frequency of the buzzer
module
2800 ± 500 Hz
Total number of signal lights (all 3
pages)
3 x 4
5.4
Operating
conditions
Operating temperature
-5 °C … +50 °C
Storage temperature
-15 °C … +50 °C
EMC
Immunity tests
Emission tests
EMC-directive 2004/108/EC
EN 61000-6-2:2005 /AC:2005
EN 61000-6-4:2007/A1:2011
Vibration/shock
EN 60068-2-6
EN 60068-2-27