BNI EIP-502-105-R015
BNI EIP-508-105-R015
EtherNet/IP™ IP67 modules
User's Guide
Page 1: ...BNI EIP 502 105 R015 BNI EIP 508 105 R015 EtherNet IP IP67 modules User s Guide...
Page 2: ...ce 6 I O Port 7 IO Link Port 7 Port 7 4 Technical Data 8 4 1 Dimensions 8 4 2 Mechanical Data 8 4 3 Operating Conditions 8 4 4 Electrical Data 8 4 5 Ethernet 9 4 6 Function Indicators 9 Module Status...
Page 3: ...Display 32 8 1 General 32 8 2 Address Specifications 32 8 3 Control and Display 32 8 4 Display Information 32 8 5 Design and Symbols 33 8 6 Startup 33 8 7 Main Menu 33 8 8 IP Setup 34 8 9 Network Conf...
Page 4: ...ing triangle The result of an action is indicated by an arrow Action instruction 1 Result of action Action instruction 2 Actions can also be indicated as numbers in parentheses 1 Step 1 2 Step 2 Synta...
Page 5: ...ndling contrary to the instructions provided in this User s Guide Obligations of the owner operator The device is a piece of equipment in accordance with EMC Class A This device can pro duce RF noise...
Page 6: ...ule 6 Port 4 IO Link standard I O 7 Pin port LED signal status 8 Port 5 IO Link standard I O 9 Port 6 IO Link standard I O 10 Port 7 IO Link standard I O 11 Port 3 IO Link standard I O 12 Port 2 IO Li...
Page 7: ...tor supply 2 24 V Module sensor supply 3 0 V GND module sensor supply 4 0 V GND actuator supply Note Where possible use a separate power source to supply the sensor bus and actuator with power Total c...
Page 8: ...uts EN 61131 2 Type 2 Note The total current of the module must not exceed 9 A Note Unused I O ports must be provided with cover caps to comply with degree of protection IP67 IO Link Port M12 A coded...
Page 9: ...ports M12 A coded 8x female Dimensions W x H x D in mm 68 x 226 x 42 9 Type of mounting Screw mounting with 2 mounting holes Ground strap installation M4 Weight Approx 670 gr 4 3 Operating Condi tion...
Page 10: ...n UA Green Output power OK Red flashing Low output power 18V Red No output power 11V US Green Input power OK Red flashing Low input power 18V Mod Green flashing Incorrect or no configuration of the mo...
Page 11: ...atus The status of the input or output pins is 1 Red flashing Short circuit Short circuit between pin 1 and 3 Red Short circuit Short circuit at dedicated pin IO Link port Green IO Link IO Link commun...
Page 12: ...balluff com 11 5 Integration Here you see an example of how the module can be integrated into a Rockwell RS Logix 5000 First go offline Right click Ethernet on the correct scanner card Select a new mo...
Page 13: ...f com 12 5 Integration Then select the general Ethernet module as the ETHERNET module in the communication path Now enter a user defined tag name to select the general format Data SINT to enter the IP...
Page 14: ...www balluff com 13 5 Integration The new module and corresponding controller tags are generated automatically Then download the configuration...
Page 15: ...the download is done you can observe and control the tags using the Controller Tags option Make sure you select the correct tag name which you configured beforehand The input output and configuration...
Page 16: ...0 1 1 Module General configuration for the entire module 2 25 2 IO Link port 1 Configuration of IO Link port 1 26 49 3 IO Link port 2 Configuration of IO Link port 2 50 73 4 IO Link port 3 Configurati...
Page 17: ...elete 0xX1 Switch on upload 0xX2 Switch on download The data of the other IO Link ports is structured identically and described in the following Cycle Settings This parameter can be used to influence...
Page 18: ...ctions disabled stored parameter data and identification data of the IO Link device are deleted Enable upload If only the upload is enabled the master always starts an upload of the parameter data In...
Page 19: ...fferent type is to be used the contents of the parameter server must be deleted The data storage is supported only by IO Link devices with IO Link Revision 1 1 Upload Flag on the IO Link De vice The u...
Page 20: ...ibute of the explicit messages Class Instance Attribute Value 245 0xF5 1 0x01 12 0x0C 0 disabled default 1 enabled Note For QuickConnect to be enabled ACD Address Conflict Detection must also be enabl...
Page 21: ...rNet IP BNI EIP 50x 105 R015 www balluff com 20 6 Configuration via Explicit Messages Rockwell Auto mation Prod ucts that are Compatible with QuickConnect Source Allen Bradley Ethernet IP QuickConnect...
Page 22: ...uickConnect slave with crossover cable Slave to slave connection using patch cable For setting up the topology only the linear topology with a maximum of 20 modules on the tool side is permitted If ne...
Page 23: ...lluff Network Interface EtherNet IP BNI EIP 50x 105 R015 www balluff com 22 6 Configuration via Explicit Messages PLC Program Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 2...
Page 24: ...www balluff com 23 6 Configuration via Explicit Messages Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 30...
Page 25: ...Balluff Network Interface EtherNet IP BNI EIP 50x 105 R015 www balluff com 24 6 Configuration via Explicit Messages Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 31...
Page 26: ...licit messages Enable Disable Fault State Class Instance Attribute Value 9 0x09 1 16 corre sponds to outputs 0 15 6 0 Fault state disabled 1 Fault state enabled Fault State Ac tion Class Instance Attr...
Page 27: ...RSLogix 5000 devices can be used to config ure an IO Link device via explicit messages For this purpose the MSG components in the PLC program are used Read IO Link Parameter Service Code Class Instan...
Page 28: ...which index is to be read In this example this is index 0x4E Destination Array Read shows the read out value In case of a configuration error the error code is likewise displayed there In the Communi...
Page 29: ...l to the previous example Read IO Link parameter The Source Length must be exactly the same length as the parameter data to be written In this example index 0x4E subindex 0 value 0x02 is written in So...
Page 30: ...nk port 2 152 199 IO Link port 3 Process data inputs at IO Link port 3 200 247 IO Link port 4 Process data inputs at IO Link port 4 248 295 IO Link port 5 Process data inputs at IO Link port 5 296 343...
Page 31: ...ved 41 SC 0 0 0 0 PDI DF VF IO Link error VF Validation failed SC IO Link short circuit DF Data storage validation failed PDI Process data invalid 42 Vendor ID 1 Vendor ID 43 Vendor ID 2 44 Device ID...
Page 32: ...ink port 3 134 165 IO Link port 4 Process data output at IO Link port 4 166 197 IO Link port 5 Process data output at IO Link port 5 198 229 IO Link port 6 Process data output at IO Link port 6 230 26...
Page 33: ...nabled from the control panel If the lock is set no more editing can be done see bit layout Chapter 6 2 Standard output data 8 2 Address Specifi cations IP address 192 168 1 1 Subnet mask 255 255 255...
Page 34: ...W 1 0 Subnet 255 255 255 000 Gateway 000 000 000 000 Hardware and firmware update Current IP Current subnet mask e Current gateway address BNI EIP 508 105 R015 Module name B A L L U F F BALLUFF Curre...
Page 35: ...ng of the editing process The completely entered address is saved by briefly pressing the Set key when edit ing the first octet The entered value appears right afterwards in the IP overview display Ma...
Page 36: ...ckers in fast scroll mode If the module receives a single ping the word Ping appears on the display for a couple of seconds Then the previous display returns You can exit ping mode sooner by briefly p...
Page 37: ...le addresses and obtain information about con nected IO Link devices as well as configure these First ensure that integration into your network has been carried out correctly For connection setup with...
Page 38: ...d network activity of the module and about the module itself You can also see here whether the display lock was set via the control unit The navigation bar appears in the upper area of the window whic...
Page 39: ...LEDs If an IO Link device is connected to one of the configured IO Link terminals some of the device data will be displayed in addition to the module data Clicking the text takes you to the Device Pro...
Page 40: ...ink port To obtain the information and the configuration of the correct IO Link device select the correct port on the right side of the module figure Tip You can monitor only the process data of the c...
Page 41: ...onfigure the parameters of the IO Link device via the Parameter Data option The parameter index and subindex of the IO Link device are described in the corresponding separate user s guide Under Events...
Page 42: ...www balluff com 41 9 Web Server 9 5 Diagnostic Mod ule The current status of the module and network appears on this page as shown on the mod ule The status is also discussed under Description...
Page 43: ...on page permits configuration of the module You can change the addresses set under DHCP Client and add your own module information texts as well as a description of the module To use the configuration...
Page 44: ...ctions 502 IP 67 IO Link master module 4 IO Link ports 508 IP 67 IO Link master module 8 IO Link ports Versions 105 display version 2 port switch Mechanical version R015 plastic housing resistant Fort...
Page 45: ...www balluff com 44 Notes...
Page 46: ...www balluff com www balluff com Balluff GmbH Schurwaldstrasse 9 D 73765 Neuhausen a d F Germany Phone 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 922508 E Edition E15 Subject to modification...