www.balluff.com
9
4
Technical Data
4.5. Ethernet
Ethernet IP port
2 x 10Base/100Base Tx
Connection for Ethernet IP port
M12, D-coded, female
Cable types in accordance with
IEEE 802.3
Shielded, twisted pair min. STP CAT 5/ STP CAT 5e
Data transmission rate
10/100 Mbps
Max. cable length
100 m
Flow control
Half-duplex/full-duplex (IEEE 802.33x pause)
4.6. Function
indicators
Module Status
LED
Display
Description
UA
Green
Output power OK
Red, flashing
Low output power (< 18V)
Red
No output power (< 11V)
US
Green
Input power OK
Red, flashing
Low input power (< 18V)
Mod
Green, flashing
Incorrect or no configuration of the module
Green
Module is working
Red, flashing
Fixed bus clock is not possible
Red-green, flashing
Initial sequence
Netw
ork
Off
Module has no IP address
Green, flashing
Module has IP, but no connection established
Green
Connection established
Red, flashing
Connection timeout
Red-green, flashing
Initial sequence
100
Off
Bus clock: 10 Mbps
Yellow
Bus clock: 100 Mbps
LNK
Green
Data transfer
Status LEDs
Port LEDs