![Balluff BNI EIP-306-000-Z010 User Manual Download Page 16](http://html1.mh-extra.com/html/balluff/bni-eip-306-000-z010/bni-eip-306-000-z010_user-manual_469609016.webp)
www.balluff.com
15
6
Process Data
6.3.
Process Data
Inputs
BNI EIP-308-
….
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
I32
I34
I22
I24
I12
I14
I02
I04
Input data (and Feedback
output)
I04
Input on port 0 pin 4
1
I72
I74
I62
I64
I52
I54
I42
I44
2
I112 I114 I102 I104
I92
I94
I82
I84
3
I152 I154 I142 I144
I132 I134 I122 I124
4
S3
S2
S1
S0
Short circuit status
00hex
no short circuit
03hex
short circuit
between Pin 1 and 3 on
stated port
5
S7
S6
S5
S4
6
S11
S10
S9
S8
7
S15
S14
S13
S12
8
O32
O34
O22
O24
O12
O14
O02
O04
Overload status
O04=1
Overload on port
0 pin 4
9
O72
O74
O62
O64
O52
O54
O42
O44
10 O112 O114 O102 O104 O92
O94
O82
O84
11 O152 O154 O142 O144 O132 O134 O122 O124
12
0
0
0
0
0
0
PS
PA
Power status
PS: Sensor power
PA: Actor power
6.4.
Process Data
Outputs
BNI EIP-308-
….
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
O32 O34 O22 O24 O12 O14 O02 O04
Output data
O04
Output on port 0 pin
4
1
O72 O74 O62 O64 O52 O54 O42 O44
2
O112 O114 O102 O104 O92 O94 O82 O84
3
O152 O154 O142 O144 O132 O134 O122 O124
4
R32 R34 R22 R24 R12 R14 R02 R04
Restart
Restart output here after a
detected overload
5
R72 R74 R62 R64 R52 R54 R42 R44
6
R112 R114 R102 R104 R92 R94 R82 R84
7
R152 R154 R142 R144 R132 R134 R122 R124
8
YF
YO
RF
RO
IPAP Control
RO: Red LED on
RF: Red LED flashing
YO: Yellow LED on
YF: Yellow LED flashing
9
PL
GO
RO
Display Control
RO: Red LED on
GO: Green LED on
PL: PLC lock active