BES 516-300-S34 _ -S4-N
Capteurs inductifs
12 V
50 mA
120 mW
30 nF
0.5 mH
Vmax
Imax
Pi
Ci
Li
Vmax (or Ui)
Imax (or Ii)
Pi
Ci + Ccable
Ci + Ccable
≤
≤
≤
≥
≥
Voc (or U0)
Isc (or Io)
Po
Ca (or Co)
La (or Lo)
=
=
=
=
=
ASSOCIATED APPARATUS
WITH ENTITY PARAMETERS
BES 516-300-S...-S4-N SERIES
INDUCTIVE PROXIMITY SWITCHES
NONHAZARDOUS (UNCLASSIFIED)
LOCATION
Class I, Division 1,
Groups A, B, C, D, T4
Class I, Zone 0, AEx ia IIC
Classe I, Division 1,
Groupes A, B, C, D, T4
Classe I, Zone 0, Ex ia IIC
T4 temperature code based on 70 °C ambient
HAZARDOUS (CLASSIFIED) LOCATION
FM Control Drawing CD 1
APPROVED BARRIER/
ASSOCIATED EQUIPMENT FOR
FM APPROVED SENSORS
APPROVED BARRIER/
ASSOCIATED EQUIPMENT FOR
CFM APPROVED SENSORS
FM-US:
FM-CA:
FM-US:
FM-CA:
Note:
temperature range -25°C to +70°C
The configuration of associated Apparatus must be FM Approved
1.
(CSA Certified or FM-Canada Approved when installed in Canada)
under Entity Concept.
BES 516-300-S...-S4-N Series may be installed within the Hazardous (Classified)
2.
location for which it is approved.
Installation in the United States should be in accordance with the
3.
National Electric Code, NFPA 70, Article 504.
Installation in Canada should be in accordance with the Canadian Electrical Code,
4.
CSA C22.1, Part 1, Appendix F.
No revision to this drawing is permitted without FM or CSA approval.
5.
2
1
NAMUR
I
v
R
Mode de protection "ia"
de sécurité intrinsèque
N°
893934
FR
·
D16
; Sous r
éserve de modifications
. Remplace edition 1410.
3
français