ADDENDUM
CommuniCare Advance & AssureCare
Fire Panel Interface
The CommuniCare Advance and AssureCare Control Panels require an Input from a Fire
Panel before allowing conversations between the Remote Units and the Panel.
The Connections should be made as follows:
To ensure correct operation both JP1 and JP2 must be fitted.
If the fire panel connections (or the Test connections to the Break Glass Unit) are not in
place the System will Commission correctly but the Control Panel will not allow
communication with Remote Units.
Note:
to allow the Control Panel to communicate with Remote Units
without
the Fire Panel
connection, link the “Test” and “0V” connections instead of fitting the Break Glass unit.