5-4 Control Wiring
MN762S
P1-08
Digital In 1
(Term 2)
Digital In 2
(Term 3)
Digital In 3
(Term 4)
Analog Input
(Term 6)
7
Open: Stop
Open: Stop
Open: Bipolar analog speed ref
Bipolar analog input
Closed: Fwd
Run
Closed: Rev Run
Closed: Preset Speed 1
8
Open: Stop
Open: Stop
Open: Preset Speed 1
Bipolar analog input
Closed: Fwd
Run
Closed: Rev Run
Closed: Bipolar analog speed ref
9
Open: Stop
Closed: Run
Fwd
Open: Stop
Closed: Reverse Run
Digital Input 3
(Term 4)
Bipolar analog
input (Term 6)
Preset Speed
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
10
Open: Stop
Open: Stop
Open: Trip
Bipolar analog input
Closed:
Forward Run
Closed: Reverse Run
Closed: No Trip
11
Open: Stop
Open: Bipolar analog
speed ref
Open: Trip
Bipolar analog input
Closed: Run
Closed: Preset Speed 1
Closed: No Trip
12
Open: Stop
Open: Preset Speed 1
Open: Trip
Bipolar analog input
Closed: Run
Closed: Bipolar analog
speed ref
Closed: No Trip
13
Normally
Open (NO)
Normally Closed (NC)
Open: Bipolar analog speed ref
Bipolar analog input
Momentarily
Close to Run
Momentarily Open to
Stop
Closed: Preset Speed 1
14
Normally
Open (NO)
Normally Closed (NC)
Normally Open (NO)
Bipolar analog input
Momentarily
Close to Run
Fwd
Momentarily Open to
Stop
Momentarily Close to Run Rev
15
Open: Stop
Open: Forward
Open: Decel Ramp 1 (P1-11)
Bipolar analog input
Closed: Run
Closed: Reverse
Closed: Decel Ramp 2 (P2-25)
16
Open: Stop
Open: Forward
Open: Decel Ramp 1 (P1-11)
Open: Preset Speed 1
Closed: Run
Closed: Reverse
Closed: Decel Ramp 2 (P2-25)
Closed: Preset
Speed 2
Table 5-3 Parameter P1-08 Control of Digital Inputs when P1-07=0 Continued
Summary of Contents for VS1MXS series
Page 1: ...03 11 Installation Operating Manual MN762S VS1MXS AC Extreme Duty Microdrive...
Page 28: ...5 10 Control Wiring MN762S...
Page 58: ...7 24 Parameter Descriptions MN762S...
Page 60: ...8 2 Customizing Your Application MN762S...
Page 80: ...D 2 Options and Kits MN762S...
Page 85: ......
Page 86: ......