3-8 Operation
21-Operating Mode - Sets the basic operation of the inverter
input terminals and keypad FWD and REV keys. The Series 10
inverter has several modes of operation to fit various application
requirements. Please refer to the following table to determine
which operating mode is right for your application. The available
options include keypad only, control terminal strip only,
combination keypad and control terminal strip operation,
electronic potentiometer, preset speeds, 2-wire control, and
3-wire control. The factory setting is “0”, keypad speed control
and keypad run FWD only.
Parameter 21-Operating Mode
Value
Speed
Control
Start
Control
Type of Control
0
Keypad
Keypad
Keypad FWD Only, 8 Speeds or 4 speeds
with Accel/Decel Select
10
Keypad
Keypad
Keypad FWD and REV, 8 Speeds or 4 speeds
with Accel/Decel Select
1
Terminals
Keypad
Keypad FWD Only, 8 Speeds or 4 speeds
with Accel/Decel Select
11
Terminals
Keypad
Keypad FWD and REV, 8 Speeds or 4 speeds
with Accel/Decel Select
2
Keypad
Terminals
2-Wire, 8 Speeds or 4 speeds with Accel/De-
cel Select
3
Terminals
Terminals
2-Wire, 8 Speeds or 4 speeds with Accel/De-
cel Select
4
Keypad
Terminals
3-Wire, 4 Speeds
5
Terminals
Terminals
3-Wire, 4 Speeds
6
Terminals
Terminals
2-Wire Electronic Pot with 1 Preset Speed or
Accel/Decel Select
7
Terminals
Terminals
3-Wire Electronic Pot
Summary of Contents for Series 10
Page 1: ...Series 10 Inverter Control Installation and Operating Manual 2 00 MN710 AC INVERTER...
Page 13: ...1 8 General Information...
Page 35: ...2 22 Installation...
Page 67: ...4 6 Troubleshooting...
Page 68: ...Section 5 Illustrations Illustrations 5 1...
Page 69: ...5 2 Illustrations...
Page 70: ...Illustrations 5 3 3 5 HP NEMA 1 230 460VAC...
Page 71: ...5 4 Illustrations...