Receiving & Installation 3-3
MN2411
Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power
before you ensure that grounds are connected. Electrical shock can cause serious or fatal
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be
connected to an approved earth ground. Local codes may also require proper grounding of
generator systems.
The NEC requires that the frame and exposed metal surfaces be at local ground reference
potential to avoid electrical shock hazard. A local ground reference may require a driven earth
ground conductor at the generator installation site. Make the ground connection as shown in
Figure 3-2. Use the appropriate size wire (normally 6 AWG) as required by NEC and local
codes. The local reference ground is normally a copper clad earth ground rod driven into the
earth at least 8 feet.
Figure 3-2 Frame Ground Connection
Engine Oil
The generator is shipped dry. This means no oil is in the engine crankcase and no fuel is in the
fuel tank. Refer to section 5 of this manual for lubricant and fuel requirements and obtain the
correct type and quantity of engine motor oil and fuel.
1.
Refer to section 5 of this manual and add the required amount of engine oil.
2.
Refer to section 5 of this manual and add the appropriate amount of fuel.
After installation, the post installation checks must be performed prior to starting the engine.
After these checks have been performed and the system operation is verified to be good, refer to
Section 5 Maintenance for periodic checks that must be performed at scheduled intervals to
ensure continued operation with minimal problems.