MN715P
Setup and Operation
4-6
Figure 4-3 Remote 0-10VDC 3 Wire Operation
J4
1
2
3
4
5
6
Reverse
Stop
Speed Command
Forward
Not used
GND
S1
Pos.
Description
5
ON
3 Wire
6
OFF
Voltage mode
7
ON
Remote Speed Ref.
8
ON
Remote commands
0-10VDC signal input
Figure 4-4 Remote 4-20mA 2 Wire Operation
J4
1
2
3
4
5
6
Reverse
Not used
+Speed Command
Forward
Not used
–Speed Command
S1
Pos.
Description
5
OFF
2 Wire
6
ON
Current mode
7
ON
Remote Speed Ref.
8
ON
Remote commands
4-20mA signal input