4-3
Setup and Operation
MN715P
S1 Settings Continued
Switch
Setting
Description
1
OFF
Base Frequency = 60Hz
1
ON
Base Frequency = 50Hz
2
OFF
Maximum frequency limit = Base Frequency (60/50Hz)
2
ON
Maximum frequency limit = 2 X Base Frequency (130 or 110 Hz)
3
OFF
Reverse motor rotation ENABLED
3
ON
Does not allow reverse motor rotation
OFF
Power up Start DISABLED (see notes)
4
ON
Power up Start ENABLED the control will resume operation as soon
as power is applied. Power up start is disabled the first time you
power up the drive (see notes).
5
OFF
Terminal 2 wire mode (If S1-8 = ON)
5
ON
Terminal 3 wire mode (If S1-8 = ON)
6
OFF
Analog input VOLTAGE (if S1-7 = ON)
6
ON
Analog input CURRENT (if S1-7 = ON)
7
OFF
Use local speed reference (front panel potentiometer)
7
ON
Use remote speed reference (J4 connector)
8
OFF
Use local commands (front panel FWD, REV, STOP)
8
ON
Use remote commands (J4 connector)
Note 1: If power up start is ON and local commands are used, the drive will resume
operation in the same FWD or REV direction when power is applied.
Note 2: If power up start is ON and remote 2 wire commands are used, the drive will
resume operation if the forward or reverse switch is still closed (2 wire).
Note 3: If power up start is ON and remote 3 wire commands are used, the drive will
not allow power up start operation (unless the momentary contacts stop and
forward or reverse are manually held closed during power up).
Note 4: After power down, if any S1 switch position is changed, power up start is
cancelled.