![Baldor 15P Series Installation And Operating Manual Download Page 13](http://html1.mh-extra.com/html/baldor/15p-series/15p-series_installation-and-operating-manual_468833013.webp)
MN715P
Receiving and Installation
3-6
115VAC 1 Phase Wire Size and Protection Devices
Table 3-5 Wire Size and Protection Devices - 1 phase
Control
Input Fuse
Wire Gauge
Control
Output
Input Fuse
Wire Gauge
Output
Rating
HP
Fast Acting
Amps
Time Delay
Amps
AWG
mm
2
0.33
10
10
14
2.08
0.5
10
10
14
2.08
0.75
15
10
14
2.08
1.0
20
15
14
2.08
Note: All wire sizes are based on 75
°
C copper wire, 1% line impedance.
Figure 3-4 Single Phase AC Power and Motor Connections
L1
N
Earth
AC Motor is not provided with control.
Baldor
Series 15P
Control
Metal conduit should be used to shield output wires
(from T1, T2, T3 of control to T1, T2, T3 of motor).
T1
T2
T3
T1
T2 T3
G
Shield wires inside a metal conduit.
Motor wire should be sized using the 3 phase
information in Table 3-4.
L1
L2
L3