Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Basic Installation and
Configuration Guidelines
Use minimum 6AWG copper conductors only.
Torque field connections between 21 and 23 in lbs.
Readily accessible disconnecting means to be provided at time of instal-
lation.
Permanently connected power supply.
Connect only to a circuit protected by a Class A Ground Fault Circuit Inter-
rupter (GFCI) or Residual Current Device (RCD) mounted at least 5’ (1.52M)
from the inside walls of the spa/hot tub and in line of sight from the
equipment compartment.
CSA enclosure: Type 2
Refer to Wiring Diagram inside the cover of the control enclosure.
Refer to Installation and Safety Instructions provided by the spa manufac-
turer.
Warning:
People with infectious diseases should not use a spa or hot
tub.
Warning:
To avoid injury, exercise care when entering or exiting the spa
or hot tub.
Warning:
Do not use a spa or hot tub immediately following strenuous
exercise.
Warning:
Prolonged immersion in a spa or hot tub may be injurious to
your health.
Warning:
Maintain water chemistry in accordance with the Manufactur-
ers instructions.
Warning:
The equipment and controls shall be located not less than 1.5
meters horizontally from the spa or hot tub.
Warning! GFCI or RCD Protection.
The Owner should test and reset the GFCI or RCD on a
regular basis to verify its function.
CSA Compliance/Conformité
Caution:
• Test the ground fault circuit interrupter before each use of the spa.
• Read the instruction manual.
• Adequate drainage must be provided if the equipment is to be installed
in a pit.
• For use only within an enclosure rated CSA Enclosure 3.
• Connect only to a circuit protected by a Class A ground fault circuit
interrupter or residual current device.
• To ensure continued protection against shock hazard, use only identical
replacement parts when servicing.
• Install a suitably rated suction guard to match the maximum flow rate
marked.
Warning:
• Water temperature in excess of 38°C may be injurious to your health.
• Disconnect the electrical power before servicing.
Attention:
• Toujours verifier l’efficacite du disjoncteur differentiel avant d’utiliser
differentiel avant d’utiliser le bain.
• Lire la notice technique.
• Lorsque l’appareillage est installe dans une fosse, on doit assurer un
drainage adequat.
• Employer uniquement a l’interieur d’une cloture CSA Enclosure 3.
• Connecter uniquement a un circuit protege par un disjoncteur differen
-
tiel de Class A.
• Afin d’assurer une protection permanente contre le danger de shock
electrique, lors de l’entretien employer seulement des pieces de rechange
identiques.
• Les prises d’aspiration doivent etre equipees de grilles convenant au
debit maximal indique.
Avertissement:
• Des temperatures de l’eau superieures a 38°C peuvent presenter un
danger pour la sante.
• Deconnecter du circuit d’alimentation electrique avante l’entretien.
Warning/Advertissement:
• Disconnect the electric power before servicing. Keep access door closed.
• Deconnecter du circuit d’alimentation electrique avant l’entretien.
Garder la porte fermer.
Warning! Qualified Technician Required for Service and Installation
Warning! Shock Hazard!
No User Serviceable Parts.
Do not attempt service of this control system. Contact your
dealer or service organization for assistance. Follow all
owner’s manual power connection instructions. Installation
must be performed by a licensed electrician and all ground-
ing connections must be properly installed.