Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual  |  6 

Copyright 2020 Baker Hughes Company. All rights reserved.

Technical Specifications

Functional

Input:

   

 

 

 

 

4-20mA (0-100%)

Output:

   

 

 

 

 

3-15 psi or 3-30 psi

 

 

 

 

 

 

 

 

Minimum output greater than 0.2psi

Supply Pressure:

 

 

 

 150psi maximum, minimum 3psi above max required output pressure

Supply Pressure Effect:

   

 

Span over full supply pressure range <0.1%

Medium: 

 

 

 

 

Standard instrument quality air to 50 micron

Air Consumption:

 

 

 

<2.5l/min (0.09 scfm) at 50% signal

Operating Temperature:

   

 

-40°C to 85°C (-40° F to +185° F)

Relative Humidity: 

 

 

0 to 100% Relative Humidity

Output Capacity: 

 

 

 

>300l/min (12scfm) delivery and exhaust at 100% signal

Maximum Terminal Voltage:

 

 

Maximum 6.5Volts

Minimum Operating Current:

 

 

Less than 3.5mA

Current Reversal Protection:

 

 

 No effect within normal 4-20mA range protected to 100mA continuous.

Insulation:

   

 

 

 

 Electrical circuits are isolated from housing. Tested to 725V DC, 100MΩ

Performance

(At 20°C (68°F), 30psi supply, 3-15psi range, for a typical instrument except otherwise stated);

Instrument Accuracy:

 

 

 

mean <0.1%

Independent Linearity:

   

 

mean <±0.05% of span

Hysteresis, Resolution & Deadband: 

mean <=0.05% of span

Accuracy Rating: 

 

 

<±0.75% span (including factory calibration error)

Above figures are in accordance with ANSI/ISA 51.1:1993; N.B. Instrument accuracy excludes calibration errors

Temperature Effect: 

 

 

 

Span and Zero

 

  

 

 

 

 

 

 Mean temperature coefficient over full operating range –40 to +85°C less than 0.035% 

span/degC

Vibration:

   

 

 

 

<3% of span; 4mm peak-peak 5-15Hz, 2g sine 15-150Hz

Mounting Position:

 

 

 

Integral bracket allows for mounting in any orientation

Long Term Stability: 

 

 

 

Span and Zero

 

 

 

 

 

 

 

Typically better than 0.25% span per year

Electromagnetic Compatibility:

   

Compliant with EC requirements:

     

 

 

 BS  EN61000-6-4

 - Generic Emissions Standard – Industrial environment

     

 

 

 

BS EN61000-6-2

 - Generic Standards – Immunity for industrial environments

 

 

 

 

 

 

 

 To meet the EMC specifications, screened cable should be used for installation. The 

cable screen should be connected to the internal earth bonding point of the I/P. An 

earth strap should also be connected from the external earth bonding point of the I/P to 

a common earth point. The cable screen should not be connected at the signal source 

when used in IS environments.

Controls: 

 

 

 

 

Span and Zero and tight shut-off trimpots with 10% adjustment

Physical
Air Supply and Output Connections: 

 1/4" NPT supply and output; 1/8" NPT exhaust baffles to allow for captured bleed

Electrical:

   

 

 

 

1/2" NPT (M20 option); 2 internal screw terminals for 2.5mm2 cable

Weight: 

 

 

 

 

 

2.07Kg

Materials

Aluminium and zinc diecasting with nitrile diaphragms, epoxy powder coat painting as standard. Weatherproof to Type 4X (IP66) 

[mounted upright]�

Summary of Contents for Masoneilan 4411 I.S.

Page 1: ...Masoneilan 4411 Series Electropneumatic Transducer Instruction Manual Baker Hughes Data Classification Public...

Page 2: ...CULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE ME...

Page 3: ...tured Bleed Version 3 Pneumatic Installation 3 Electrical Installation 4 Wiring and Cable Entry 4 Conduit Entry 4 Calibration 4 Tight Shut Off Adjustment Instructions 5 Simple Functional Checks 5 Tech...

Page 4: ...ne Warranty Items sold by Baker Hughes are warranted to be free from defects in materials and workmanship for a period of one year from the date of shipment provided said items are used according to B...

Page 5: ...rocess control applications The units operate a closed loop system incorporating a feedback sensor ensuring long term stability and high accuracy performance with fail safe operation i e the output fa...

Page 6: ...be blocked with paint and or plastic sheeting etc Captured Bleed Version The baffles and the baffle cover are fitted to maintain the adequate Ingress Protection IP rating of the instrument Removal of...

Page 7: ...conforming to explosion proof specifications must be used A ground terminal is provided both internally and externally and should be used if ground continuity is essential The unit is supplied with pl...

Page 8: ...p pressure 0psi adjust potentiometer slowly clockwise until the output pressure falls to zero Do not turn the pot beyond this point The shut off point is now set Shut off point check Increase the inpu...

Page 9: ...accordance with ANSI ISA 51 1 1993 N B Instrument accuracy excludes calibration errors Temperature Effect Span and Zero Mean temperature coefficient over full operating range 40 to 85 C less than 0 0...

Page 10: ...III Division 2 Group FG T6 Ta 75 C T5 Ta 85 C CSA Class I Division 1 Group BCD Class II Group EFG Class III Ta 85 C T5 Ta 65 C T6 Class I Division 1 Group ABCD Class II Group EFG Class III Ta 85 C T4...

Page 11: ...being adversely affected thus ensuring that the type of protection is not compromised Aggressive substances e g acidic liquids or gases that may attack metals or solvents that may affect polymeric ma...

Page 12: ...9 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved...

Page 13: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 10 Copyright 2020 Baker Hughes Company All rights reserved...

Page 14: ...11 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved Notes...

Page 15: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 12 Copyright 2020 Baker Hughes Company All rights reserved Notes...

Page 16: ...ormation The Baker Hughes logo and Masoneilan are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or trademarks of their re...

Reviews: