8 | Baker Hughes
© 2019 Baker Hughes Company. All rights reserved.
▪
Cable temperature: must be mentioned if the ambient temperature is greater than 70°C:
Ambient Temperature
Cable Temperature
75 °C
80 °C
80 °C
85 °C
6. ELECTRICAL CONNECTIONS and CONDUIT ENTRY
The type 12400 must be installed and put into service in conformance with
EN/IEC 60079-14
and / or
national and local regulations applicable for explosive atmospheres.
6.1. Voltage supply allowable
Connect the wires to the instrument's terminals, taking care of complying with pola and -
and maximum voltage allowed mentioned in the table below. Make the earth connections with
the internal and external ground terminals.
Voltage Supply U (V)
AO_1
AO_2
DO_1/DO_2
MINI
MAXI
MINI
MAXI
MINI
MAXI
Flameproof
10V
40V
10V
30 V
0.5V
30V
Intrinsic Safety
10V
30V
10V
30V
0.5V
30V
6.2. Maximum Power
3 W inside the 12400 housing.
6.3. Output current and loop resistor
o
AO_1 et AO_2:
3.8mA to 20.5mA for measurement
< 3.6mA or > 21mA in case of fault
o
Maximum loop resistor
For AO_1 et AO_2 : R maxi (
) = U (V)
– 10 (V)
I max (A)
R charge
U
o
DO_1 et DO_2
Open collector output. Maximum current is 1A. A load resistor must be inserted in the loop
to limit the current to this maximum.
6.4. Intrinsic Safety entity parameters
AO_1:
terminal identification:
Primary OUT 4- 20 mA
Max. Input Voltage
Ui
30
V
Max. Input Current
Ii
125
mA
Max. Input Power
Pi
900
mW
Max. Internal Capacitance
Ci
2.0
nF
Max. Internal Inductivity
Li
500
µH