Cable temperature: must be mentioned if the ambient temperature is greater than 70°C: 

Ambient Temperature 

Cable Temperature 

75 °C 

80 °C 

80 °C 

85 °C 

 
6.  ELECTRICAL CONNECTIONS and CONDUIT ENTRY 

The type 12400 must be installed and put into service in conformance with 

EN/IEC 60079-14

 and / or 

national and local regulations applicable for explosive atmospheres. 
 

6.1. Voltage supply allowable 

Connect the wires to the instrument's terminals, taking care of complying with pola and -
and maximum voltage allowed mentioned in the table below. Make the earth connections with 
the internal and external ground terminals. 

Voltage Supply   U (V)

 

AO_1 

AO_2 

DO_1/DO_2 

MINI 

MAXI 

MINI 

MAXI 

MINI 

MAXI 

Flameproof 

10V 

40V 

10V 

30 V 

0.5V 

30V 

Intrinsic Safety 

10V 

30V 

10V 

30V 

0.5V 

30V 

 

6.2. Maximum Power 

3 W inside the 12400 housing. 

 

6.3. Output current and loop resistor 

o

 

AO_1 et AO_2: 

3.8mA to 20.5mA for measurement 
< 3.6mA or > 21mA in case of fault 

o

 

Maximum loop resistor

  

For AO_1 et AO_2 : R maxi (

) = U (V) 

– 10 (V) 

  

 

 

 

 I max (A)

 

 

 

R charge

U

 

o

 

DO_1 et DO_2 

Open collector output. Maximum current is 1A. A load resistor must be inserted in the loop 
to limit the current to this maximum. 

 

6.4. Intrinsic Safety entity parameters 

 

AO_1: 

terminal identification: 

Primary OUT 4- 20 mA

 

Max. Input Voltage 

Ui 

30 

Max. Input Current 

Ii 

125 

mA 

Max. Input Power 

Pi 

900 

mW 

Max. Internal Capacitance 

Ci 

2.0 

nF 

Max. Internal Inductivity 

Li 

500 

µH 

 

Summary of Contents for Masoneilan 12400 Series

Page 1: ...nsmitter Controller ATEX Instruction Manual Safety Guide Rev A bis Advanced Level Measurement SIL2 capable Liquid Level Transmitter Low and high level switch integrated functions Easy installation and...

Page 2: ...REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN...

Page 3: ...6 3 Output current and loop resistor 8 6 4 Intrinsic Safety entity parameters 8 6 5 Conduit entry in flameproof application 9 7 ASSEMBLY AND INSTALLATION 10 7 1 Assembly 10 7 2 12400 flameproof instal...

Page 4: ...Verify material compatibility with the application Ensure proper use of fall protection when working at heights per Safe Site Work Practices Ensure use of proper Personal Protective Equipment Take the...

Page 5: ...sel Flanged 5 Top and side Screwed BW or SW 6 Side and bottom Screwed BW or SW 7 Side and bottom Flanged 8 Top and side Flanged 9 Side and side Screwed BW or SW 1 FM FMc SI NI DIP XP and Nema 4X 6P 2...

Page 6: ...6 Baker Hughes 2019 Baker Hughes Company All rights reserved 3 2 Schematics and parts identification Torqu e Tube Mechanism Compartment Digital Compartment...

Page 7: ...nd IECEx Certificate of Conformity WARNING POTENTIAL DANGER OF ELECTROSTATIC CHARGES SEE INSTRUCTIONS 5 ATEX FLAMEPROOF MARKING FOR TYPE 12400 The marking is on the serial plate stamped on the 12400 h...

Page 8: ...ns with the internal and external ground terminals Voltage Supply U V AO_1 AO_2 DO_1 DO_2 MINI MAXI MINI MAXI MINI MAXI Flameproof 10V 40V 10V 30 V 0 5V 30V Intrinsic Safety 10V 30V 10V 30V 0 5V 30V 6...

Page 9: ...an be done with different variations taking into account approved manufacturer and requested approvals A cable entry of a certified type Ex d IIC Ex tb IIIC can be mounted directly on the single NPT A...

Page 10: ...E SUPPLY FROM CONTROL SYSTEM Hazardous Zones 1 2 21 22 Non Hazardous Zone 7 3 12400 Intrinsic Safety and type n installation The 12400 may be installed in gas and dust explosive atmospheres of groups...

Page 11: ...perations comply with the instrument s intended use Refer to ANNEX II for the pushbutton menu flowchart Please refer to the 12400 Instruction and Operation Manual IOM GEA19367 to complete the followin...

Page 12: ...ce the defective parts with genuine manufacturer s replacement parts only Check that the pressure limiting plug at the back of the mechanism compartment rep 190 and its spongy gasket rep 192 are prese...

Page 13: ...ospheres For use in dusty hazardous areas zones 20 21 22 the user will have to clean regularly the different sides of the enclosure to avoid the deposits of dusts the maximum thickness must be 5 mm Th...

Page 14: ...of the 12400 described 6 4 10 3 For Flameproof For ambient temperature greater than 70 C the user must choose a cable entry and a cable compatible with Ambient Temperature Cable and Cable Entry Temper...

Page 15: ...2019 Baker Hughes Company All rights reserved Masoneilan 12400 DLT ATEX Instruction Manual 15 ANNEX I...

Page 16: ...MATIC POWER ON To BAS SETUP Menu To ADV SETUP Menu VIEW DATA To VIEW ERR Menu To FAILSAFE Menu If any critical default remains RESET Lock Lock Lock CTRL SP ALTERNATING DISPLAY SETUP Lock CTRL SP SIGNA...

Page 17: ...s Jacksonville Florida Phone 1 904 570 3409 Deer Park Texas Phone 1 281 884 1000 Fax 1 281 884 1010 Houston Texas Phone 1 281 671 1640 Fax 1 281 671 1735 valves bhge com Copyright 2019 Baker Hughes Co...

Reviews: