INTRODUCTION
I-E96-424A
E - 1
APPENDIX E - DIGITAL SLAVE OUTPUT MODULE
(IMDSO04)
INTRODUCTION
The IMDSO04 uses an NTDI01 for termination. Dipshunts on
the termination unit configure the digital outputs that are sent
to the process. The Digital Slave Output (DSO) module can
switch a voltage of 24 VDC at 250 mA.
Figure
shows an NTDI01 point configuration dipshunt
without
strapping, and the digital signal path from the DSO
module to the field device for a termination unit application.
Refer to Table
to determine the dipshunt strapping to con-
figure your application. Figure
ment and polarity for each of the digital output signals. Refer to
this figure when connecting field wiring to the NTDI01.
Figure E-1. NTDI01 to IMDSO04 Diagram
E1
E1
E2 E
CO M
E
CO M
T00660A
IMDSO04
(REPRESENTATIVE
CIRCUIT)
NKTU01
NTDI01
FIELD
WIRING
FIELD
DEVICE
+5 VDC
P3
P1
+
+
–
–
LOAD
TERMINAL
BLOCKS
TB1-TB4
1
2
3
4
5
6
7
8
DIPSHUNTS
XU1-XU16