DIGITAL SLAVE OUTPUT MODULE (IMDSO01/02/03)
DIGITAL SLAVE OUTPUT MODULE (IMDSO01/02/03)
D - 2
I-E96-424A
®
Table D-1. NTDI01 with IMDSO01/02/03Dipshunt
Configuration
Application/Signal Type
Dipshunt Configuration
XU1, 3, 5, 7, 9, 11, 13, 15
Externally Powered
System Powered from E1
System Powered from E2
NOTES:
1. XU17 does not require a dipshunt for this application.
2. Care must be taken when powering solid state relay loads through the E1 and E2 connectors.
The traces on the termination unit allow for two amperes for all outputs driven from either E1 or E2.
Exceeding this current can damage the termination unit printed circuit board. Where higher current
is required, use the externally powered configuration.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
T00657A
1
2
3
4
5
6
7
8
NOTE: DO = Digital Output
Figure D-2. NTDI01 with IMDSO01/02/03 Terminal Assignments
TERMINAL
NUMBER
TB4
TB2
TB1
TB3
DIPSHUNT
USED
XU13
XU15
T00658A
DO1
DO2
1
2
3
4
5
6
7
8
–
–
+
+
DIPSHUNT
USED
XU9
XU11
DO3
DO4
–
–
+
+
DIPSHUNT
USED
XU5
XU7
DO7
DO8
–
–
+
+
DIPSHUNT
USED
XU1
XU3
DO5
DO6
–
–
+
+