INSTALLATION
SETUP/INSTALLATION
2 - 8
I-E96-440A
®
To install the cable follow these steps.
1. Verify IMASI03 is unplugged from the MMU backplane.
2. Connect the hooded end (J1) of the cable (NKAS01 or
NKAS11) to the MMU backplane. To do this, insert the connec-
tor into the same backplane slot as assigned to the slave mod-
ule. Snap the latches securely into place.
3. Insert the male 36 pin connector (J2) end of the cable into
the P1 connector of the TU. The cable should latch securely in
place.
4. Insert the male 24 pin connector (J3) end of the cable into
the P2 connector of the TU. The cable should latch securely in
place.
5. Slide the IMASI03 into the MMU until the module is fully
seated and the faceplate is flush with the front of the rack.
Figure 2-5. Cable Connections for NTAI06
T00723A
P1
P3
J3
P2
2
P1
3
J2
J1
P2
NKAS01/11
(NOTE 1)
ANALOG SLAVE
TERMINATION UNIT CABLE
NTAI06
CHANNELS 11-16
CHANNELS 1-10
IMASI03
FIELD
WIRING
NOTES:
1. NKAS01 HAS PVC INSULATION (SPECIFY LENGTH UP TO 200 FT).
NKAS11 HAS NON-PVC INSULATION (SPECIFY LENGTH UP TO 200 FT).
2. P2 IS CONNECTED TO INPUT CHANNELS 11 THROUGH 16.
3. P1 IS CONNECTED TO INPUT CHANNELS 1 THROUGH 10.
Table 2-4. NTAI06 Cable Applications
Nomenclature/
Description
Application
Connector
Maximum
Length
NKAS01 (PVC)
Connects TU to
IMASI03
P1 and P2 on TU
to MMU
backplane.
61 m
(200 ft)
NKAS11
(non-PVC)
Connects TU to
IMASI03
P1 and P2 on TU
to MMU
backplane.
61 m
(200 ft)