INTRODUCTION
NOMENCLATURE
I-E96-440A
1 - 5
NOMENCLATURE
Table
contains the modules and equipment that can be
used with the NTAI06:
SPECIFICATIONS
Refer to Table
for the specifications of the NTAI06 Termina-
tion Unit.
Table 1-3. Nomenclature
Nomenclature
Description
IEFAS01
INFI 90 Fastener Kit
IMASI03
Universal Analog Input Slave Module
NKAS01
Cable, Termination Unit (PVC)
NKAS11
Cable, Termination Unit (non-PVC)
NFTP01
Field Termination Panel
Table 1-4. Specifications
Property
Characteristic/Value
Power Requirements
+ 24 VDC required if system powered 4 - 20 mA
inputs are used.
Mounting
Mounts in the Field Termination Panel (NFTP01).
Environmental
Electromagnetic/Radio Frequency Interference
Ambient Temperature
Relative Humidity
Atmospheric Pressure
Air Quality
No values available at this time. Keep cabinet doors
closed. Do not use communication equipment closer
than 2 meters from the cabinet.
0° to 70° C (32° to 158° F)
5% to 90% ± 5% up to 55° C (131° F)
(non-condensing)
5% to 40% ± 5% at 70° C (158° F) (non-condensing)
Sea level to 3 km (1.86 miles)
Noncorrosive
Cooling Requirements
No cooling is necessary when used in Bailey
Controls cabinets and operated within stated limits.
Certification
CSA certified for use as process control equipment in
an ordinary (nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE