INTRODUCTION
I-E96-408A
B - 1
APPENDIX B - LOOP INTERFACE
MODULE CONFIGURATION (INLIM03)
INTRODUCTION
The Loop Interface Module (INLIM03) uses the NICL01 to termi-
nate its connection to Plant Loop. A termination cable
(NKLS04) connects the LIM to the ICL. The ICL provides a place
to connect either coaxial or twinaxial cable from the communi-
cation loop. This appendix contains figures and tables that
show the dipswitch locations on the LIM and their settings and
is provided as a quick reference for personnel installing the
NICL01. Figure
shows the dipswitch locations on the LIM
circuit board. Tables
list the event counter and
error counter addresses for dipswitch S1. Table
lists PCU
addresses set by dipswitch S2. Refer to the INLIM03 instruc-
tion for more detailed installation and configuration
information.
Figure B-1. Loop Interface Module Component Locations
Table B-1. LIM Event Counter Addresses (S1)
Counter
Address
Hex
Address
Switch Positions
(Binary Address)
1 2 3 4 5 6 7 8
Description
48
30
0 0 1 1 0 0 0 0
Total messages transmitted, including
forwarding.
49
31
0 0 1 1 0 0 0 1
Transmit retries.
50
32
0 0 1 1 0 0 1 0
Composite BIM Receive/Transmit 4 bits each.
Receive is viewed at the top LED.
51
33
0 0 1 1 0 0 1 1
Messages taken from the BIM transmit buffer.
S2
PCU ADDRESS
P4
RIBBON CABLE
ATTACHES HERE
T00361A
XU4
S1
OPTION SWITCH
EDGE
CONNECTORS
P1
P3
P2
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8