![Bailey infi 90 Modular Power System II Instruction Download Page 41](http://html1.mh-extra.com/html/bailey/infi-90-modular-power-system-ii/infi-90-modular-power-system-ii_instruction_3468074041.webp)
INTRODUCTION
I-E96-427B
C - 1
APPENDIX C - IMMFC05 MULTI-FUNCTION CONTROLLER
INTRODUCTION
Several dipswitches must be set for the IMMFC05 Multi-Func-
tion Controller. Figure
shows the IMMFC05 module layout.
Tables
,
explain the dipswitch settings for the
board. For more information on the module, refer to the
IMMFC05 Multi-Function Controller Module
product
instruction.
NOTE:
Jumpers J17 through J22 are factory set (jumper pins one
and two) and should not be changed. Jumpers J23 and J24 are
reserved for future use. The positions of J23 and J24 do not affect
module operation.
Figure C-1. IMMFC05 Module Layout
T00024A
P1
P2
P3
STATUS
LED
GROUP
LEDS
XU39
SW4
OPTIONS
SW3
MODULE ADDRESS
STOP
RESET
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
Table C-1. Example IMMFC05 Dipswitch SW3
Module Address Settings
Address
Example
Dipswitch Position
(Binary Value)
1
1
(128)
2
2
(64)
3
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
7
1
Y
X
0
0
1
1
1
15
1
Y
X
0
1
1
1
1
31
1
Y
X
1
1
1
1
1
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. Position 1 must be set open for proper operation.
2. Y = 0 for normal execution mode, 1 for diagnostic mode.
3. X = Not important.