INTRODUCTION
I-E96-427B
2 - 1
SECTION 2 - INSTALLATION
INTRODUCTION
This section lists the steps to properly install the NTMF01
Multi-Function Controller Termination Unit (TMF). The instal-
lation procedure includes physical installation, dipshunt con-
figuration, cable connection, power wiring and handling. To
properly install the TMF termination unit do the steps in this
section in the order they appear.
SPECIAL HANDLING
Observe these steps when handling electronic circuitry:
NOTE: Always use Bailey's field static kit (part number 1948385A1 -
consisting of two wrist straps, ground cord assembly, alligator clip,
and static dissipative work surface) when working with the modules.
The kit grounds a technician and the static dissipative work surface
to the same ground point to prevent damage to the modules by elec-
trostatic discharge.
1.
Use Static Shielding Bag.
Keep the modules in the static
shielding bag until you are ready to install them in the system.
Save the bag for future use.
2.
Ground Bag Before Opening.
Before opening a bag con-
taining an assembly with CMOS devices, touch it to the equip-
ment housing or a ground to equalize charges.
3.
Avoid Touching Circuitry.
Handle assemblies by the
edges; avoid touching the circuitry.
4.
Avoid Partial Connection of CMOS Device.
Verify that all
devices connected to the modules are properly grounded before
using them.
5.
Ground Test Equipment
.
6.
Use an Antistatic Field Service Vacuum.
Remove dust
from the module if necessary.
7.
Use a Grounded Wrist Strap.
Connect the wrist strap to
the appropriate grounding plug on the power entry panel. The
grounding plug on the power entry panel is connected to the
earth grounding electrode system through the AC safety
ground.
8.
Do Not Use Lead Pencils to Set Dipswitches.
To avoid
contamination of dipswitch contacts that can result in unnec-
essary circuit board malfunction, do not use a lead pencil to
set a dipswitch.