INSTALLATION
TERMINATION UNIT (MODULE) CONFIGURATION AND INSTALLATION
3 - 10
I-E96-620A
®
TERMINATION UNIT (MODULE) CONFIGURATION AND INSTALLATION
Two of the interface modules (INLIM03, INSIM01) require ter-
mination. The INSIM01 terminates with the NTCU01. The
INLIM03 terminates with the NTCL01 or NICL01. Appendices
and
contain disphunt configuration information for the
NTCL01 and NICL01. There are no dipshunts on the NTCU01.
Refer to the Termination Instructions, I-E96-408 (NICL01) or
I-E96-422 (NTCL01), for complete information about installing
the termination module or unit.
NOTE: Use a standard RS-232-C cable with DB-25 connectors
when connecting the computer or terminal to the NTCU01.
INSTALLING THE INTERFACE MODULES
If the switch settings on the interface modules are complete,
they are ready to be installed in the Module Mounting Unit
(MMU).
Installing the INSIM01
To install the SIM:
1. Verify the SIM slot assignment in the MMU.
2. Attach the hooded end of the cable (NTKU01 for the
NTCU01) to the MMU backplane cable connector opening for
the SIM. The other end of the cable attaches to the termination
unit.
3. Guide the top and bottom edges of the circuit card along
the top and bottom rails of MMU.
4. Slide the module into the slot; push the module until the
front panel is flush with the top and bottom of the MMU frame.
5. Turn the two captive latches a half turn to lock the module
in place.
WARNING
Disconnect power before installing dipshunts for slave mod-
ules on the MMU backplane (slave expander bus). Failure to do
so could result in severe or fatal shock.
AVERTISSEMENT
Couper l'alimentation avant d'installer les dipshunts sur la
plaque arrlere du chassis de montage de modules (MMU).
Toute negligence a cet egard constitue un risque de choc pou-
vant entrainer des blessures graves, voire moretlles.