INSTALLATION
INIIL02 INFI-NET TO INFI-NET LOCAL INTERFACE INSTALLATION
3 - 20
I-E96-607A
®
INIIT03 DIPSWITCH LLB3, DIAGNOSTICS
Dipswitch LLB3 selects certain operating options and enables
diagnostics that are meaningful to qualified Bailey Controls
Company service personnel.
All switch positions on LLB3 should be set as shown for normal
operation. Table
shows the dipswitch settings for LLB3.
Verify that all dipswitch positions on LLB3 are set as marked in
the user setting column.
Table 3-10. INIIT03 Dipswitch LMB2, Module Options
Pole
1
2
3
4
5
6
7
8
Function
User
Setting
0
1
ROM checksumming enabled.
ROM checksumming disabled.
0
0
0
1
1
0
1
1
Diagnostic port (P4) data characteristics:
8 data bits, 1 stop bit, no parity.
8 data bits, 1 stop bit, even parity.
8 data bits, 1 stop bit, odd parity.
8 data bits, 2 stop bits, no parity.
0
0
0
1
1
0
1
1
Exception reporting rate (time between scans):
2.0 seconds.
1.0 second.
0.5 second.
0.25 second.
0
1
No failover to secondary module on power system status
alarm.
Failover to secondary module on power system status
alarm.
1
0
1
Not used. Must be set as shown.
Not used.
0
0
1
No redundancy.
Redundancy configured.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-11. INIIT03 Dipswitch LLB3, Diagnostics
Pole
1
2
3
4
5
6
7
8
Function
User
Setting
0
1
NIS handshake time-out enabled.
NIS handshake time-out disabled.
0
1
Not used. Must be set as shown.
Not used.
0