INTRODUCTION
SPECIFICATIONS
I-E96-316A
1 - 5
SPECIFICATIONS
Power Requirements
Voltage
+5 VDC (
±
5%)
+15 VDC (-2.5%, +5%)
-15 VDC (-5%, +2.5%)
+24 VDC (
±
10%)(from termination unit/termination module)
Current (maximum)
332 mA (+5 VDC)
35 mA (+15 VDC)
30 mA (-15 VDC)
50 mA (+24 VDC)
Dissipation
1.65 W @ +5 VDC
525 mW @ +15 VDC
450 mW @ -15 VDC
1.20 W @ +24 VDC
Digital I/O
Digital Inputs (3)
Optically isolated
Current (typical)
4.5 mA @ 24 VDC
5.0 mA @ 125 VDC
7.0 mA @ 120 VAC rms @ 60 Hz
Voltage
24 VDC (
±
10%)
125 VDC
(±
10%)
120 VAC
(±
10%)
Turn-On Voltage (minimum)
24 VDC
21.4 VDC
125 VDC
95.0 VDC
120 VAC
85.0 VAC
Turn-Off Voltage (maximum)
24 VDC
12 VDC
125 VDC
60 VDC
120 VAC
42 VAC
Maximum Input Current at Minimum Turn-On
24 VDC
3 mA @ 21.4 VDC
125 VDC
3 mA @ 95.0 VDC
120 VAC
5 mA @ 85.0 VAC 60 Hz
Off Leakage Current (maximum)
24 VDC
10
µ
A (@ Vin
≤
12 VDC)
125 VDC
10
µ
A (@ Vin
≤
60 VDC)
120 VAC
1.6 mA (@ Vin
≤
42 VAC 60 Hz)
Response Time
DC "Fast" - 1.5 ms
DC "Slow" - 17 ms