INTRODUCTION
I-E96-316A
5 - 1
SECTION 5 - TROUBLESHOOTING
INTRODUCTION
This section explains the error indications and corrective
actions for the Quick Response Slave (QRS) module.
ERROR INDICATIONS AND CORRECTIVE ACTION
You can obtain the status of the QRS through an INFI 90 oper-
ator interface (e.g., Operator Interface Station, Engineering
Work Station, Configuration and Tuning Terminal) or the front
panel module status LED indicator.
Status LED
The front panel status LED has three states to indicate normal
operation and error conditions. Table
lists QRS status LED
states, error indications, probable causes and corrective
actions.
NOTE:
If the corrective actions in Table
do not correct a problem
with the QRS module, replace the slave module.
Master Module Errors
The Multi-Function Processor (MFP) performs status checks on
the QRS. An error will appear in the report function of an oper-
ator interface. Refer to the Product Instruction for the operator
interface you are using for an explanation of these reports.
Table 5-1. Status LED Indications and Corrective Actions
LED State
Indication
Probable Cause
Corrective Action
Solid Green
Slave module operating
normally and communi-
cating with MFP
Normal operation
No action required
Off
Slave module not enabled Address set on S1 not the
same as address in MFP
configuration FC 79 spec 1
Change address on S1 to corre-
spond with FC 79 spec 1
OR
Change address in FC 79 spec 1
to correspond with S1
Dipshunt not properly
installed between MFP mod-
ule and slave module
Verify dipshunt is installed prop-
erly (no bent pins) in slave
expander bus socket on MMU
backplane between MFP and
slave module
MFP configuration is not cor-
rect
Verify FC 79 is in MFP configura-
tion