INTRODUCTION
I-E96-322A
7 - 1
SECTION 7 - MAINTENANCE
INTRODUCTION
The reliability of any stand-alone product or control system is
affected by the maintenance of the equipment. Bailey Controls
Company recommends that all equipment users practice a pre-
ventive maintenance program that will keep the equipment
operating at an optimum level.
This section presents procedures that can be performed
on-site. These preventive maintenance procedures should be
used as guidelines to assist you in establishing good preventive
maintenance practices. Select the minimum steps required to
meet the cleaning needs of your system.
Personnel performing preventive maintenance should meet the
following qualifications.
•
Maintenance personnel should be qualified electrical tech-
nicians or engineers that know the proper use of test equip-
ment and how to handle electronic circuitry.
•
Maintenance personnel should know turbine shutdown
and start-up, and plant operating procedures.
PREVENTIVE MAINTENANCE SCHEDULE
Table
is the preventive maintenance schedule for the
IMHSS03 Hydraulic Servo Module. The table lists the preven-
tive maintenance tasks in groups according to their specified
maintenance interval. Some tasks in Table
are self explan-
atory. Instruction for tasks that require further explanation are
covered under
PREVENTIVE MAINTENANCE PROCEDURES
NOTE: The preventive maintenance schedule is for general pur-
poses only. Your application may require special attention.
Table 7-1. Preventive Maintenance Schedule
Task
Frequency
Check the HSS module and module mounting unit for dust. Clean as necessary using an anti-
static vacuum.
3 months
Check all signal, power and ground connections associated with the HSS module and its ter-
mination unit or module. See procedure.
Inspect the HSS module and associated termination unit or module, giving particular attention
to power supply contacts and edge connectors. Clean as necessary. See procedure.
12 months
Calibrate the LVDT and hydraulic actuator. See procedure.
As needed
Complete all tasks in this table.
Shutdown