INTRODUCTION
I-E96-310B
7 - 1
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
Repair procedures are limited to module replacement. If the
DSO module fails, remove and replace it with another. This
section also explains how to replace a failed digital output fuse.
Verify that the replacement module dipswitch is set the same
as that of the failed module.
MODULE REPLACEMENT PROCEDURE
Follow Steps 1 through 8 to replace the DSO module. Observe
the steps listed in
handling the module.
1. Verify all digital output signals from the associated control
module are disabled.
2. Turn the 2 latching screws on the defective module
1
/
2
-turn
either way to release them.
3. Grasp the screws and slide out the module.
4. Set the dipswitch on the replacement module to match the
settings of the defective module.
5. Verify the appropriate digital output fuses are installed.
WARNING
If input or output circuits are a shock hazard after disconnect-
ing system power at the power entry panel, then the door of the
cabinet containing these externally powered circuits must be
marked with a warning stating that multiple power sources
exist.
AVERTISSEMENT
Si des circuits d'entrée ou de sortie sont alimentés à partir de
sources externes, ils présentent un risque de choc électrique
même lorsque l'alimentation du système est débranchée du
panneau d'entrée d'alimentation. Le cas échéant, un avertisse-
ment signalant la présence de sources d'alimentation multiples
doit être apposé sur la porte de l'armoire.
CAUTION
Disable the module output signals before removing the mod-
ule. Damage to the module may result.
ATTENTION
Il est nécessaire de désactiver les signaux de sortie du module
avant de le retirer de sa position. Un manquement à cette pré-
caution pourrait endommager le module.