INSTALLATION
SETUP AND PHYSICAL INSTALLATION
I-E96-310B
3 - 3
Dipswitch S1 Settings
Dipswitch S1 sets the I/O expander bus address of the DSO
module. This address uniquely identifies the DSO module to
the control module and must be the same as the address set in
the control module function block (function code 83, specifica-
tion S1) configuration.
Dipswitch S1 is a six-pole address dipswitch. Pole one is the
most significant bit and pole six is the least significant bit.
Valid addresses are zero to 63 (refer to Table
). Record the
dipswitch S1 settings in the space provided.
Fuses
The DSO module contains eight fuses, one for each output.
These fuses protect the module and equipment connected to
the module from current surges and short circuits. Table
lists the types of fuses used in the IMDSO01, IMDSO02 and
IMDSO03 modules. Verify the fuses are of the proper type and
are installed.
NOTE: A fuse does not need to be installed for unused digital out-
puts.
Table 3-1. DSO Dipswitch S1 Settings
Address
Example
Dipswitch Pole
(Binary Value)
1
2
3
4
5
6
(32)
(16)
(8)
(4)
(2)
(1)
0
0
0
0
0
0
0
31
0
1
1
1
1
1
63
1
1
1
1
1
1
User setting
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-2. Fuse Ratings
Module Type
Fuse Number
Fuse Type
IMDSO01
194776_24001
4.0 A, 250 V, slow-blow
IMDSO02
194776_13001
3.0 A, 250 V, normal
IMDSO03
194776_11501
1.5 A, 250 V, normal