INSTALLATION
INSERTING THE FCS IN THE MODULE MOUNTING UNIT
3 - 4
I-E96-314A
®
INSERTING THE FCS IN THE MODULE MOUNTING UNIT
To install the module in the module mounting unit:
1. Verify the module mounting unit slot assignment for the
module.
2. Check the slave expander bus dipshunt socket on the
backplane of the MMU. The dipshunt must be installed with all
pins shorted. This provides a communication path from the
master module to the slave module.
3. Guide the top and bottom edges of the circuit card along
the top and bottom rails of the MMU.
4. Slide the module into the slot. Push until the module is
seated in the backplane connector. Turn the two thumbscrews
on the faceplate a half turn until the module locks in place.
CONFIGURATION
The controller or processor module must have Function Code
145 in its configuration to be able to communicate with the
FCS. Configure the controller before attempting to operate the
FCS. Refer to the Function Code Applications Manual
E93-900-20 for information about Function Code 145.
Function Code Specifications
The Function Code Applications Manual lists the function code
specifications, output blocks and configuration information.
The operation/configuration manual for the operator interface
you are using lists configuration instructions. Refer to those
manuals for specific information about the steps listed below.
1. Determine the specification settings for Function Code 145
in advance.
2. Reserve four blocks for the outputs of Function Code 145.
3. Choose the specifications that will configure the MFP to
properly interface the FCS in the system.
4. Enter the configuration into the system.