In addition to conventional charging procedures, the following requirements shall be
followed.
–
Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimise the amount of
refrigerant contained in them.
–
Cylinders shall be kept upright.
–
Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
–
Label the system when charging is complete (if not already).
–
Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak test
shall be carried out prior to leaving the site.
9. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample
shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is
essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
•
Mechanical
handling
equipment
is
available,
if
required,
for
handling
refrigerant
cylinders;
•
All personal protective equipment is available and being used correctly;
•
The recovery process is supervised at all times by a competent person;
•
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer's instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure
that the cylinders and the equipment are removed from site promptly and all isolation
valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it
has been cleaned and checked.
Summary of Contents for JHS-A019-07KR2/E
Page 1: ...1 Bahag No 26507950 26506966 Item No JHS A019 07KR2 E ...
Page 26: ...26 AIRE ACONDICIONADO PORTÁTIL Manual de instrucciones ...
Page 51: ...51 PORTABLE AIR CONDITIONER Instruction Manuel ...
Page 57: ...57 III Control Setting 排 热 管 Exhaust Pipe Assembly Window Sealing Plate Assembly ...
Page 77: ...77 ПРЕНОСИМ КЛИМАТИК Ръководство с инструкции ...
Page 103: ...103 HORDOZHATÓ KLÍMABERENDEZÉS Használati utasítás ...
Page 127: ...127 PŘENOSNÁ KLIMATIZACE Uživatelská příručka ...
Page 149: ...149 TRANSPORTABELT KLIMAANLÆG Brugsvejledning ...
Page 154: ...154 Det maksimale antal enheder der må opbevares sammen bestemmes af lokale regler ...
Page 173: ...173 TEISALDATAV KLIIMASEADE Kasutusjuhend ...
Page 196: ...196 SIIRRETTÄVÄ ILMASTOINTILAITE Käyttöohje ...
Page 218: ...218 CLIMATISEUR MOBILE Manuel d instructions ...
Page 243: ...243 PRENOSIVI KLIMA UREĐAJ Upute za uporabu ...
Page 267: ...267 FÆRANLEG LOFTRÆSTING Leiðbeiningarhandbók ...
Page 290: ...290 CONDIZIONATORE D ARIA PORTATILE Manuale di istruzioni ...
Page 314: ...314 DRAAGBARE AIRCONDITIONER Gebruiksaanwijzing ...
Page 338: ...338 BÆRBART KLIMAANLEGG Bruksanvisning ...
Page 362: ...362 PRENOSNÁ KLIMATIZAČNÁ JEDNOTKA Návod na obsluhu ...
Page 385: ...385 PRENOSNA KLIMATSKA NAPRAVA Navodila za uporabo ...