Interface Module XC
Protocol Converter / User Manual
Page 9 from 12
E130506819092
Baer Energie- & Messtechnik GmbH
Siemensstr. 3
D-90766 Fürth
Phone +49 911 970590
Fax +49 911 9705950
Technical data
Housing:
Polycarbonate housing with terminals for using with EMH LZQJ-XC and
DMTZ-XC meters for residential and industrial applications
Degree of protection:
IP20 (according to IEC 60529)
Protection class:
2
Temperature range:
-25°C to +55°C (operational)
-40°C to +80°C (storage temperature)
Relative humanity:
0..95%, non-condensing
Dimensions:
Ca. 50mm x 105mm x 27mm (W x H x D)
Nominal voltage:
Internal power supply from LZQJ-XC or DMTZ-XC meter
M-Bus load:
1,5mA, max. voltage: 56VDC
Battery:
None
Installation:
Exchangeable during the meter operation
LED displays:
3 LEDs:
(green)
Power/Tx: power / transmit data via M-Bus
(yellow) Rx:
receive data via M-Bus
(red)
Error:
internal communication error
Interface:
M-Bus (2 wires, passive) according to DIN EN 13757-2 (Physical Layer)
Alternative: BFC-Bus (BAER Field Control, 56VDC)
Baud rate:
300 to 9600 baud (fixed baud rate)
Data format:
8E1
Data readout:
Internal service data list / table TS
Transmission protocol:
According to DIN EN 13757-3:2013-08 (Application Layer) with fixed
baud rate
Order number:
#12760
Accessories:
Bus Master / Repeater / Mini-Master
AMR-Software: SIGLON © / Field Control Center: Meter2SCADA ©