Interface Module XC Modbus
Protocol Converter / User Manual
Page 7 from 10
E120103819092
Baer Energie- & Messtechnik GmbH
Siemensstr. 3
D-90766 Fürth
Phone +49 911 970590
Fax +49 911 9705950
Example for read out meter data:
Service data TS (/4! with completion character CR LF):
/EMH4\@\201LZQJL001VE
0.0.1(00000123)
Address/Start register: 0, Value: 123
1.25(0.00*kW)
Address/Start register: 2, Value: 0
3.25(0.00*kvar)
Address/Start register: 4, Value: 0
9.25(0.00*kVA)
Address/Start register: 6, Value: 0
31.25(0.02*A)
Address/Start register: 8, Value: 2
51.25(0.01*A)
Address/Start register: 10, Value: 1
71.25(0.01*A)
Address/Start register: 12, Value: 1
32.25(0.59*V)
Address/Start register: 14, Value: 59
52.25(0.50*V)
Address/Start register: 16, Value: 50
72.25(246.07*V)
Address/Start register: 18, Value: 24607
13.25(0.00*P/S)
Address/Start register: 20, Value: 0
14.25(50.01*Hz)
Address/Start register: 22, Value: 5001
C.86.0(38307030)
Address/Start register: 24, Value: 38307030
C.86.6(B05800F0)
Address/Start register: 26, Value: 58000
Modbus registers:
Register
address
Value
Comments
0
0
OBIS-Register 0.0.1:
123
(:= 0 + 123, Modbus ID-Address)
1
007F
Hex
(:= 0123
Dec
)
2
0
OBIS-Register 1.25:
0
kW (:= 0 + 0)
3
0
4
0
OBIS-Register 3.25:
0
kvar (:= 0 + 0)
5
0
6
0
OBIS-Register 9.25:
0
kVA (:= 0 + 0)
7
0
8
0
OBIS-Register 31.25:
0.02
A (:= 0 + 2)
9
2
10
0
OBIS-Register 51.25:
0.01
A (:= 0 + 1)
11
1
12
0
OBIS-Register 71.25:
0.01
A (:= 0 + 1)
13
1
14
0
OBIS-Register 32.25:
0.59
V (:= 0 + 59)
15
003B
Hex
(:=59
Dec
)
16
0
OBIS-Register 52.25:
0.50
V (:= 0 + 50)
17
0032
Hex
(:=50
Dec
)
18
0
OBIS-Register 72.25:
246.07
V (:= 0 + 24607)
19
601F
Hex
(:=24607
Dec
)
20
0
OBIS-Register 13.25:
0
P/S (:= 0 + 0)
21
0
22
0
OBIS-Register 14.25:
50,01
Hz (:= 0 + 5001)
23
1389
Hex
(:=5001
Dec
)
24
0248
Hex
(:= 584
Dec
)
OBIS-Register C.86.0:
38307030
(:= (584 × 65536) + 34006)
25
84D6
Hex
(:= 34006
Dec
)
26
0
OBIS-Register C.86.6:
58000
(:= 0 + 58000, characters B and
F will be clear in the string B05800F0)
27
E290
Hex
(:= 58000
Dec
)
28
FFFF
Hex
(:= 65535
Dec
)
Not used registers
29
FFFF
Hex
(:= 65535
Dec
)
...
FFFF
Hex