Installation
Mains voltage
230 VAC 50 - 60 Hz
Terminal: Connection for:
N
Mains neutral conductor N
L
Mains phase conductor L
R1
Function see page 23
R2
without function
R3I
without function
R3
without function
The PE protective conductor must be
connected to the PE metal terminal
block!
max. 12 V
Netzseite
230 VAC
D. Klemmplan für elektrischen Anschluss
Low voltage max.
12 VAC/DC
Terminal
Connection for
S1 (2x) without function
S2 (2x) without function / Option:
Temp.-sensor only display
S3 (2x) without function
S4 (2x) Release contact for Easytronic **
V1
0-10 V output for fi lter pump
(via frequency converter) ***
Z0
Pump off
Z1
Pump level 1
Z2
Pump level 2
Z3
Pump level 3
** (Insert a bridge here if not needed)
*** (Speed control for pump)
Low voltage
Relais Mains